Effect of Temperature on Frequency Dependent Dielectric Parameters of Oil-paper Insulation Under Non-sinusoidal Excitation

被引:32
作者
Pradhan, A. K. [1 ]
Chatterjee, B. [1 ]
Chakravorti, S. [1 ]
机构
[1] Jadavpur Univ, Dept Elect Engn, Kolkata 700032, W Bengal, India
关键词
Sinusoidal excitation; non-sinusoidal excitation; complex capacitance; dissipation factor; harmonics component; cross-over point; oil-paper insulation; condition monitoring; PART I; DOMAIN; SPECTROSCOPY; MOISTURE; TIME;
D O I
10.1109/TDEI.2013.003602
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Frequency domain spectroscopy is a potential tool for non-invasive condition assessment of oil-paper insulation in power equipment. On the other hand, it is well known that the results of frequency domain spectroscopy are affected predominantly by temperature. Moreover, the voltage used for frequency domain spectroscopy is sinusoidal is nature. But the actual insulation system at site is stressed by voltage that may deviate significantly from sinusoid during operation. Considering these two aforesaid facts, in this paper, the response of oil-paper insulation has been studied at different temperatures using both sinusoidal as well as non-sinusoidal excitation. An experimental sample has been prepared in the laboratory that emulates the composite insulation of oil immersed type power transformer at site. The results of frequency response using sinusoidal voltage waveform at different temperature show good agreement with the conventional results that validates the scheme of the experimental setup. Some more information is obtained from the response of non-sinusoidal excitation that could help to get a better interpretation of the actual physical condition of oil-paper composite insulation.
引用
收藏
页码:653 / 661
页数:9
相关论文
共 20 条
  • [1] Field experiences with measurements of dielectric response in frequency domain for power transformer diagnostics
    Blennow, J
    Ekanayake, C
    Walczak, K
    García, B
    Gubanski, SM
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (02) : 681 - 688
  • [2] *CIGR TASK FORC, 2002, ELECTRA, P25
  • [3] Frequency response of oil impregnated pressboard and paper samples for estimating moisture in transformer insulation
    Ekanayake, Chandima
    Gubanski, Stanislaw M.
    Graczkowski, Andrzej
    Walczak, Krzysztof
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (03) : 1309 - 1317
  • [4] On the Frequency Domain Dielectric Response of Oil-paper Insulation at Low Temperatures
    Fofana, I.
    Hemmatjou, H.
    Meghnefi, F.
    Farzaneh, M.
    Setayeshmehr, A.
    Borsi, H.
    Gockenbach, E.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (03) : 799 - 807
  • [5] Garton C. G., 1941, J I ELECT ENG LONDON, V88, P33
  • [6] Gubanski S. M., 2004, 1501 CIGRE TASK FORC
  • [7] Jaya M., 2010, 20 AUSTR U POW ENG C, P1
  • [8] Modeling the polarization spectrum in composite oil paper insulation systems
    Jota, PRS
    Islam, SM
    Jota, FG
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1999, 6 (02) : 145 - 151
  • [9] Dielectric response of mineral oil impregnated cellulose and the impact of aging
    Linhjell, Dag
    Lundgaard, Lars
    Gafvert, Uno
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2007, 14 (01) : 156 - 169
  • [10] Diagnosis of moisture in oil/paper distribution cables-part I: Estimation of moisture content using frequency-domain spectroscopy
    Neimanis, R
    Eriksson, R
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) : 9 - 14