Extinguishment of hydrogen laminar diffusion flames by water vapor in a cup burner apparatus

被引:1
作者
Feng, Ming-Hui [1 ]
Qin, Jun [1 ]
机构
[1] Univ Sci & Technol China, State Key Lab Fire Sci, Hefei 230026, Anhui, Peoples R China
基金
中国国家自然科学基金;
关键词
Hydrogen safety; Diffusion flame; Water vapor; Nitrogen; Flame suppression; OXYGEN-NITROGEN EXPLOSIONS; MIST; SUPPRESSION; EXTINCTION; MICROGRAVITY; MECHANISMS; MODEL; FIRE; AIR;
D O I
10.1016/j.jlp.2015.10.004
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
Transient computations with full hydrogen chemistry were performed to reveal the flame structure and extinguishment process of co-flow, hydrogen diffusion flame suppressed by water vapor. As the concentration of water vapor was increased, the flame detached away from the burner brim and formed an edge flame at the flame base. Water vapor showed larger chemical inhibition effect than nitrogen when extinguishing hydrogen flame, which was attributed to its enhanced third body effect in the reaction H + O-2+ M = HO2 + M. The minimum extinguishing concentration (MEC) of water vapor and nitrogen was predicted by Senecal formula and perfectly stirred reactor (PSR) model respectively. The MECs predicted by PSR model agree with the MECs calculated by Fluent, which shows that 1) the flame extinction is controlled by the flame base, and 2) radiation absorption is negligible. The measured MECs are in a reasonable agreement with the values calculated by Fluent, which demonstrates the accuracy of the CFD model. A simple model was used to investigate the relative importance of extinguishing mechanisms of water vapor. The results show that in a co-flow configuration the thermal cooling and chemical inhibition effect are the main extinguishing mechanisms in suppressing hydrogen diffusion cup burner flame. (C) 2015 Published by Elsevier Ltd.
引用
收藏
页码:260 / 267
页数:8
相关论文
共 25 条