Study of frequency domain dielectric properties of vegetable oil and mineral oil transformer

被引:5
作者
Li, Linduo [1 ]
Ren, Qiaolin [2 ]
Xiao, Sa [2 ]
Yang, Wenyan [3 ]
Xiong, Wei [1 ]
Fu, Boqiao [4 ]
机构
[1] Three Gorges Univ, Coll Elect Engn & New Energy, Yichang 443002, Peoples R China
[2] State Grid Hubei Elect Co Ltd, Xiaogan Elect Power Supply Co, Xiaogan 432100, Peoples R China
[3] Three Gorges Univ, Med Coll, Yichang 443002, Peoples R China
[4] Hubei Engn Univ, Coll Chem & Mat Sci, Xiaogan 432100, Peoples R China
来源
JOURNAL OF ENGINEERING-JOE | 2019年 / 16期
关键词
D O I
10.1049/joe.2018.8876
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
To study the properties of vegetable oil transformer, the mineral and vegetable insulation oil two transformers with the same parameters are studied using the frequency domain spectroscopy (FDS) method. The complex capacitance and the dielectric loss factor are tested by the insulation diagnostic equipment IDAX300, these parameters can reflect the insulation properties of the transformer. The experimental results show that properties of vegetable oil transformer are different to the mineral. The complex capacitance and the dielectric loss factor tan of vegetable oil transformer are higher than those of mineral oil transformer, and the moisture content in vegetable oil is higher than that in mineral oil. The test results are also emphatically analysed, which ultimately laid a theoretical foundation for large-scale operation of vegetable oil transformers.
引用
收藏
页码:1599 / 1601
页数:3
相关论文
共 15 条
  • [1] Dielectric Spectroscopy Techniques as Quality Control Tool: A Feasibility Study
    Bouaicha, A.
    Fofana, I.
    Farzaneh, M.
    Setayeshmehr, A.
    Borsi, H.
    Gockenbach, E.
    Beroual, A.
    Aka, Ngnui Thomas
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2009, 25 (01) : 6 - 14
  • [2] [董明 Dong Ming], 2015, [中国电机工程学报, Proceedings of the Chinese Society of Electrical Engineering], V35, P6246
  • [3] [董明 Dong Ming], 2015, [中国电机工程学报, Proceedings of the Chinese Society of Electrical Engineering], V35, P1002
  • [4] JONSCHER AK, 1996, UNIVERSAL RELAXATION, P143
  • [5] [李剑 Li Jian], 2015, [高电压技术, High Voltage Engineering], V41, P353
  • [6] Li X., 1988, ELECT OIL
  • [7] Liao Rui-jin, 2010, High Voltage Engineering, V36, P2869
  • [8] Liao Rui-jin, 2010, Proceedings of the CSEE, V30, P113
  • [9] Deriving an equivalent circuit of transformers insulation for understanding the dielectric response measurements
    Saha, TK
    Purkait, P
    Müller, F
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (01) : 149 - 157
  • [10] Review of condition assessment of power transformers in service
    Wang, M
    Vandermaar, AJ
    Srivastava, KD
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2002, 18 (06) : 12 - 25