Development of a Novel Dual Temperature Model for Insulation Aging in Oil Immersed Transformers

被引:8
作者
Mehta, Amit Kumar [1 ]
Naresh, R. [1 ]
Chauhan, Sushil [1 ]
机构
[1] Natl Inst Technol Hamirpur, Dept Elect Engn, Hamirpur, Himachal Prades, India
关键词
Power transformers; prorated models; thermal models; aging temperature; aging time; oil insulation; paper insulation; PAPER;
D O I
10.1109/TDEI.2015.005050
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Power transformer is one of the most expensive equipments in a high voltage AC power system. Adequate monitoring system for power transformers can help in reducing the failure rate and thereby enhancing system reliability and economic efficiency. The failure of power transformer has serious consequences on system reliability. Long term and comprehensive testing cannot be done in working transformer, so prorated model of transformer is preferred. In the proposed work, a new dual temperature test cell is developed based on IEC 62332 and IEEE C57.100. The cell provides for a current carrying conductor wrapped with insulating paper and further insulation is provided with high-density pressboard as per arrangements in power transformer. In this paper a new mathematical model is developed using activation energy and pre-exponential constant calculated from experimental results at different temperatures. The expected life based on degree of polymerization (DP) value, shows nonlinear aging of insulation based on investigation carried out on prorated model.
引用
收藏
页码:2723 / 2736
页数:14
相关论文
共 22 条
[1]  
[Anonymous], 623322 IEC TS
[2]  
[Anonymous], 2008, 623321 IEC TS, P2005
[3]  
[Anonymous], 2011, C571001999 IEEE
[4]  
[Anonymous], 2013, 67921992 IS
[5]  
[Anonymous], 2010, 3351993 IS
[6]  
Bates D. M., 1988, Nonlinear regression analysis and its applications, V2
[7]   The electrical strength of transformer oil in a transformerboard-oil system during moisture non-equilibrium [J].
Buerschaper, B ;
Kleboth-Lugova, O ;
Leibfried, T .
2003 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2003, :269-272
[8]  
Ding H. Z., 2005, 3rd IEE International Conference on Reliability of Transmission and Distribution Networks (RTDN 2005), P315, DOI 10.1049/cp:20050059
[9]   REVIEW OF CHEMICAL INDICATORS OF DEGRADATION OF CELLULOSIC ELECTRICAL PAPER INSULATION IN OIL-FILLED TRANSFORMERS [J].
EMSLEY, AM ;
STEVENS, GC .
IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY, 1994, 141 (05) :324-334
[10]  
Hernadi A., 1982, CELL CHEM TECHNOL, V16, P27