Linear programming optimization of heat distribution in a district-heating system by valve adjustments and substation retrofit

被引:36
作者
Bojic, M [1 ]
Trifunovic, N [1 ]
机构
[1] Univ Kragujevac, Masinski Fak, YU-34000 Kragujevac, Yugoslavia
关键词
D O I
10.1016/S0360-1323(99)00013-X
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The unbalanced distribution of heat in a district-heating system may be caused by the increase of hydraulic resistance of pipe network, decrease of heat transmittance of radiators inside buildings, and increase of heat transmittance of building envelope. This situation yields the overheating of some buildings and underheating of other buildings. A district-heating system is analyzed that consists of heat plant, primary pipe network, substation, secondary pipe network, and three buildings. A steady-state, bottom-up approach and the sequential linear programming is used to solve this optimization problem. Results show that significant improvement of thermal comfort may be reached by adjusting the valves of secondary pipe network and resizing of the substation heat exchanger. (C) 1999 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:151 / 159
页数:9
相关论文
共 5 条
[1]   Mixed integer linear programming optimization of heat distribution within a local heating system [J].
Bojic, M ;
Trifunovic, N .
INDOOR AND BUILT ENVIRONMENT, 1997, 6 (05) :282-290
[2]  
BOJIC M, 1996, MANUAL PROCESS ENG T, V8
[3]  
GUSTAVSSON L, 1994, THESIS U LUND SWEDEN
[4]   OBJECTIVE CRITERIA FOR THERMAL COMFORT [J].
MAYER, E .
BUILDING AND ENVIRONMENT, 1993, 28 (04) :399-403
[5]  
VANDERPLAATS GN, 1972, NUMERICAL OPTIMIZATI