Low voltage ride-through capability improvement of DFIG-based wind turbines under unbalanced voltage dips

被引:45
作者
Rahimi, Mohsen
Parniani, Mostafa [1 ]
机构
[1] Sharif Univ Technol, Dept Elect Engn, Power Syst Dynam & Control Lab, Tehran, Iran
关键词
Wind turbine; DFIG; Ride-through capability; Stator damping resistor; Unbalanced voltage dip; Rotor-side converter; FED INDUCTION GENERATOR; STABILITY ANALYSIS; POWER-SYSTEMS; ENHANCEMENT; DYNAMICS; SCHEME; FAULTS;
D O I
10.1016/j.ijepes.2014.02.035
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a competent and effective scheme to enhance the ride-through capability of DFIG-based wind turbines under unbalanced voltage dip conditions. The proposed method is realized through joint use of the rotor-side converter control and a three-phase stator damping resistor (SDR) placed in series with the stator windings. By means of an asymmetrical SDR idea, during the unbalanced voltage dip the SDR resistors are activated only in phase(s) experiencing low voltage. Then, the rotor current is controlled such that no unbalance voltage appears on the stator voltage. The proposed ride-through approach limits the peak values of the rotor inrush current, electromagnetic torque and DFIG transient response at the times of occurrence and clearing the fault. It also suppresses fluctuation of the electromagnetic torque and DFIG transient response appeared during unbalanced voltage dips due to negative sequence component. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:82 / 95
页数:14
相关论文
共 28 条
[1]   Optimal tracking and robust power control of the DFIG wind turbine [J].
Abdeddaim, S. ;
Betka, A. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2013, 49 :234-242
[2]   Algorithms for characterizing measured three-phase unbalanced voltage dips [J].
Bollen, MHJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (03) :937-944
[3]   Different methods for classification of three-phase unbalanced voltage dips due to faults [J].
Bollen, MHJ ;
Zhang, LD .
ELECTRIC POWER SYSTEMS RESEARCH, 2003, 66 (01) :59-69
[4]   Specification of rotor side voltage source inverter of a doubly-fed induction generator for achieving ride-through capability [J].
Chondrogionnis, S. ;
Barnes, M. .
IET RENEWABLE POWER GENERATION, 2008, 2 (03) :139-150
[5]  
Engelhardt S, 2011, IEEE GEN M JUL US
[6]   Enhanced Fault Ride-Through Method for Wind Farms Connected to the Grid Through VSC-Based HVDC Transmission [J].
Feltes, Christian ;
Wrede, Holger ;
Koch, Friedrich W. ;
Erlich, Istvan .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2009, 24 (03) :1537-1546
[7]   A fault tolerant doubly fed induction generator wind turbine using a parallel grid side rectifier and series grid side converter [J].
Flannery, Patrick S. ;
Venkataramanan, Giri .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2008, 23 (03) :1126-1135
[8]   Unbalanced Voltage Sag Ride-Through of a Doubly Fed Induction Generator Wind Turbine With Series Grid-Side Converter [J].
Flannery, Patrick S. ;
Venkataramanan, Giri .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2009, 45 (05) :1879-1887
[9]  
G-Bellmunt O, 2008, IEEE T ENERGY CONVER, V23, P1036
[10]   A comprehensive review on the grid integration of doubly fed induction generator [J].
Jadhav, H. T. ;
Roy, Ranjit .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2013, 49 :8-18