Optimal thermal management of server cooling system based cooling tower under different ambient temperatures

被引:93
作者
He, Wei [1 ]
Zhang, Jifang [1 ]
Li, Hailong [1 ,2 ]
Liu, Shengchun [1 ]
Wang, Yulin [1 ]
Lv, Baoying [1 ]
Wei, Jie [1 ]
机构
[1] Tianjin Univ Commerce, Tianjin Key Lab Refrigerat Technol, Tianjin 300134, Peoples R China
[2] Malardalen Univ, Future Energy Ctr, Sch Business Soc & Engn, Vasteras, Sweden
基金
中国国家自然科学基金;
关键词
Server dissipation; Thermal management; Cooling tower; Energy consumption; Ambient temperature; INTEGRATED-SYSTEM; HEAT SINK; PERFORMANCE; SIMULATION; POWER; PIPE; LOOP; FLOW;
D O I
10.1016/j.applthermaleng.2022.118176
中图分类号
O414.1 [热力学];
学科分类号
摘要
To develop a highly efficient and energy-saving cooling system in a data center, this study investigates the optimal thermal management both on the internal server cooling cycle and external cold source water cycle under different ambient temperatures based on the principle of minimal power consumption. Taking a server cabinet of 4.8 kW as the case, an internal indirect water-cooled heat sink cycle and an external cooling tower cold source cycle are constructed. A hybrid thermal management model combined with a heat dissipation model and a power consumption model was developed with the aid of MATLAB and TRNSYS. Using this model, the relationship between the chip dissipation performance attached to the fin-type heat sink and the energy consumption performance of the cooling system under different water working conditions and ambient temperatures was analyzed. Finally, to achieve minimal system energy consumption, the optimized inlet temperature and water flow rates corresponding to different ambient temperatures were obtained by fitting expressions that can better serve the optimal design of data center cooling systems. Furthermore, when the optimal value was applied using the year-round temperature of Tianjin, China in the case study, a 21.3% reduction in power consumption and a 4.43% decrease in the power usage effectiveness can be achieved compared to the case without optimization. Therefore, significant power can be saved in a data center cooling system through thermal management optimization.
引用
收藏
页数:10
相关论文
共 32 条
[1]   Transient simulation of wet cooling strategies for a data center in worldwide climate zones [J].
Agrawal, Aayush ;
Khichar, Mayank ;
Jain, Sanjeev .
ENERGY AND BUILDINGS, 2016, 127 :352-359
[2]  
ASME PTC Committee, 2018, CONFERENCE
[3]   A case study and critical assessment in calculating power usage effectiveness for a data centre [J].
Brady, Gemma A. ;
Kapur, Nikil ;
Summers, Jonathan L. ;
Thompson, Harvey M. .
ENERGY CONVERSION AND MANAGEMENT, 2013, 76 :155-161
[4]   Experimental and numerical analysis for potential heat reuse in liquid cooled data centres [J].
Carbo, Andreu ;
Oro, Eduard ;
Salom, Jaume ;
Canuto, Mauro ;
Macias, Mario ;
Guitart, Jordi .
ENERGY CONVERSION AND MANAGEMENT, 2016, 112 :135-145
[5]   Thermodynamic analysis of hybrid cooling system integrated with waste heat reusing and peak load shifting for data center [J].
Chen, Hua ;
Peng, Yu-hang ;
Wang, Yan-ling .
ENERGY CONVERSION AND MANAGEMENT, 2019, 183 :427-439
[6]   Reliability and availability assessment and enhancement of water-cooled multi-chiller cooling systems for data centers [J].
Cheung, Howard ;
Wang, Shengwei .
RELIABILITY ENGINEERING & SYSTEM SAFETY, 2019, 191
[7]  
Copeland D., 2000, Sixteenth Annual IEEE Semiconductor Thermal Measurement and Management Symposium (Cat. No.00CH37068), P266, DOI 10.1109/STHERM.2000.837093
[8]   A review of current status of free cooling in datacenters [J].
Daraghmeh, Hafiz M. ;
Wang, Chi-Chuan .
APPLIED THERMAL ENGINEERING, 2017, 114 :1224-1239
[9]   Effect of climate conditions on the thermodynamic performance of a data center cooling system under water-side economization [J].
Diaz, Andres J. ;
Caceres, Rodrigo ;
Torres, Rodrigo ;
Cardemil, Jose M. ;
Silva-Llanca, Luis .
ENERGY AND BUILDINGS, 2020, 208
[10]   Simulation of a temperature adaptive control strategy for an IWSE economizer in a data center [J].
Durand-Estebe, Baptiste ;
Le Bot, Cedric ;
Mancos, Jean Nicolas ;
Arquis, Eric .
APPLIED ENERGY, 2014, 134 :45-56