Chiller sequencing control with enhanced robustness for energy efficient operation

被引:63
作者
Sun, Yongjun [1 ]
Wang, Shengwei [1 ]
Huang, Gongsheng [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Kowloon, Hong Kong, Peoples R China
关键词
Chiller sequencing control; Energy efficiency; Reliability; Maximum cooling capacity;
D O I
10.1016/j.enbuild.2009.07.023
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper presents a strategy for improving the reliability and the energy efficiency of chiller sequencing control based on the total cooling load measurement of centralized multiple centrifugal chiller plants. The improvement is achieved as follows. Firstly, a fused measurement of building cooling load is used to replace the direct/indirect measurement. Secondly, the maximum cooling capacity of individual chillers is computed online using a simplified centrifugal chiller model. Thirdly, the online computed maximum cooling capacity is calibrated according to the quality of the fused measurement in order to deal with the possible misbehaviours in measurement instruments. A simplified model for computing the maximum cooling capacity is developed and validated using field data. The performance of the proposed chiller sequencing control strategy is tested and compared with a conventional chiller sequencing control algorithm. Test results are presented showing that the proposed strategy can effectively improve the reliability of chiller sequencing control and reduce the energy consumption of chiller plants. (C) 2009 Elsevier B.V. All rights reserved.
引用
收藏
页码:1246 / 1255
页数:10
相关论文
共 15 条
[1]  
[Anonymous], ENG MAN AUT CONTR CO
[2]  
[Anonymous], ASHRAE T
[3]  
Brown R.N., 2005, COMPRESSORS SELECTIO
[4]   Optimal chiller loading by genetic algorithm for reducing energy consumption [J].
Chang, YC ;
Lin, JK ;
Chuang, MH .
ENERGY AND BUILDINGS, 2005, 37 (02) :147-155
[5]   Performance analysis and improvement of air-to-water chiller for application in wide ambient temperature range [J].
Ding, GL ;
Fu, L .
APPLIED THERMAL ENGINEERING, 2005, 25 (01) :135-145
[6]  
Gordon J.M., 2000, Cool Thermodynamics: The Engineering and Physics of Predictive, Diagnostic and Optimization Methods for Cooling Systems
[7]   Enhancing the Reliability of Chiller Control Using Fused Measurement of Building Cooling Load [J].
Huang, Gongsheng ;
Wang, Shengwei ;
Sun, Yongjun .
HVAC&R RESEARCH, 2008, 14 (06) :941-958
[8]   A data fusion scheme for building automation systems of building central chilling plants [J].
Huang, Gongsheng ;
Wang, Shengwei ;
Xiao, Fu ;
Sun, Yongjun .
AUTOMATION IN CONSTRUCTION, 2009, 18 (03) :302-309
[9]  
Kwan C, 2001, master thesis
[10]   Energy analysis of commercial buildings in subtropical climates [J].
Lam, JC .
BUILDING AND ENVIRONMENT, 2000, 35 (01) :19-26