Comparison of Legiolert and a Conventional Culture Method for Detection of Legionella pneumophila from Cooling Towers in Quebec

被引:19
作者
Barrette, Isabelle [1 ]
机构
[1] EnvironeX Grp, 2325 Fernand Lafontaine Blvd, Longueuil, PQ J4N 1N7, Canada
关键词
PROBABLE NUMBER METHOD; ENUMERATION;
D O I
10.5740/jaoacint.18-0245
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
Background: Legionnaires' disease is a potentially lethal pneumonia contracted through inhalation of aerosolized water contaminated with Legionella bacteria. Detection and control of L. pneumophila, the primary species responsible for the disease, is critical to public health. In Quebec, cooling towers and evaporative condensers are required to follow a maintenance and testing program to ensure L. pneumophila concentrations remain at acceptable levels. Objective: This study compared a new culture method based on the most probable number approach, Legiolert (R), with the formal culture method used at EnvironeX for regulatory compliance testing to quantify L. pneumophila from cooling tower waters in Quebec. Methods: A split-sample analysis was performed in which 401 samples from cooling towers in Quebec were tested with both methods. Results: Results with 74 positive samples showed that Legiolert provided a significant increase in sensitivity for L. pneumophila compared with the agar plate method. Cooling tower samples often contain non-Legionella flora that necessitate multiple treatment and plating conditions to prevent interference with the test. Legiolert showed little to no impact from non-Legionella organisms in this study. Conclusions: Overall, Legiolert showed several advantages over the agar plate method, including increased sensitivity, reduced interference, a simplified test procedure, and an easy-to-read positive signal.
引用
收藏
页码:1235 / 1240
页数:6
相关论文
共 17 条
[1]  
Adams Deborah A, 2016, MMWR Morb Mortal Wkly Rep, V63, P1, DOI 10.15585/mmwr.mm6354a1
[2]  
American Public Health Association, 2007, STANDARD METHODS EXA, P28
[3]  
American Society of Heating Refrigerating and Air-Conditioning Engineers, 2015, 1882015 ANSIASHRAE
[4]  
Bartram Jamie, 2007, P1
[5]  
European Centre for Disease Prevention and Control, 2016, LEG DIS EUR 2014
[6]   Legionella and Legionnaires' disease:: 25 years of investigation [J].
Fields, BS ;
Benson, RF ;
Besser, RE .
CLINICAL MICROBIOLOGY REVIEWS, 2002, 15 (03) :506-+
[7]  
Gomcz-Lus R., 1993, LEGIONELLA CURRENT S, P265
[8]  
Health and Safety Executive, 2014, HSG274 HLTH SAF EX
[9]  
International Organization for Standardization, 2017, 117312017 ISO
[10]   Pseudomonas aeruginosa Las quorum sensing autoinducer suppresses growth and biofilm production in Legionella species [J].
Kimura, Soichiro ;
Tateda, Kazuhiro ;
Ishii, Yoshikazu ;
Horikawa, Manabu ;
Miyairi, Shinichi ;
Gotoh, Naomasa ;
Ishiguro, Masaji ;
Yamaguchi, Keizo .
MICROBIOLOGY-SGM, 2009, 155 :1934-1939