A scale model to evaluate water evaporation from indoor swimming pools

被引:58
作者
Asdrubali, F. [1 ]
机构
[1] Univ Perugia, Dept Ind Engn, I-06125 Perugia, Italy
关键词
Evaporation; Heat loads; Swimming pools; Scale model; SURFACE;
D O I
10.1016/j.enbuild.2008.10.001
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The evaluation of water evaporation from indoor swimming pools is a topic of considerable practical interest, since evaporation may cause the highest energy consumption of the pool plant. A purposely designed experimental apparatus was used to measure the water evaporation rate from a pool scale model inserted into a climatic chamber to control environmental conditions. The experimental data were obtained varying various parameters such as water temperature, air temperature, relative humidity and air velocity. The results were used to propose a prediction model for water evaporation which was compared to other methods found in the literature, showing a good agreement. (C) 2008 Elsevier B.V. All rights reserved.
引用
收藏
页码:311 / 319
页数:9
相关论文
共 21 条
[1]  
[Anonymous], ASHRAE T
[2]  
[Anonymous], 1999, ASHRAE HDB HVAC APPL
[3]   Comparative study of energy regulations for buildings in Italy and Spain [J].
Asdrubali, F. ;
Bonaut, M. ;
Battisti, M. ;
Venegas, M. .
ENERGY AND BUILDINGS, 2008, 40 (10) :1805-1815
[4]  
ASDRUBALI F, 2004, ATT 21 C NAZ UN IT T
[5]  
ASHRAE, 1989, 6289 ASHRAE
[6]  
Biasin K., 1974, Electrowaerme International, V32, pA115
[7]  
Carrier W.H., 1918, ASHVE Transactions, V24, P25
[8]  
COTANA F, 2000, HEAT TECHNOLOGY, V18, P69
[9]  
Hanssen S.O., 1990, P ROOMV 90 OSL
[10]  
Incropera F.P., 1996, FUNDAMENTAL HEAT MAS, VFourth