摘要
The objectives of this paper are to analyze the heat transfer characteristics during the NH3-H2O absorption process in plate heat exchangers and to develop the experimental correlations of the heat transfer coefficient for the compression/absorption hybrid heat pump application. The parametric analysis on the effects of the absorber internal pressure, ammonia weak solution concentration and absorber geometric dimensions on the absorber capacity and system COP (coefficient of performance) is carried out. From the experimental results, the maximum absorber capacity of 7.3 kW, COP of 2.66 and the maximum hot water outlet temperature of 80.7 degrees C are obtained. It is concluded that the heat transfer coefficient of solution side increases with increasing the aspect ratio (L/D) while it does not significantly depend upon the aspect ratio (W/D). Finally, an experimental Nusselt number correlation is developed with +/- 20% error band and compared with the other correlation from the literature. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:371 / 378
页数:8
相关论文
共 24 条
  • [11] Ammonia-water absorption in vertical tubular absorbers
    Fernández-Seara, J
    Sieres, J
    Rodríguez, C
    Vázquez, M
    [J]. INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2005, 44 (03) : 277 - 288
  • [12] Groll EA, 1997, ASHRAE TRAN, V103, P361
  • [13] INFLUENCE OF THE SOLUTION HEAT EXCHANGER EFFICIENCY ON THE PERFORMANCE OF A SINGLE EFFECT H2O-LiBr ADIABATIC ABSORPTION SYSTEM
    Gutierrez Urueta, Geydy
    Rodriguez Aumente, Pedro
    Rodriguez Hidalgo, Maria
    Lecuona Neumann, Antonio
    [J]. INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2011, 19 (02) : 107 - 112
  • [14] Herbine GS, 1995, ASHRAE TRAN, V101, P1324
  • [15] Hodgett D., 1987, P 17 INT C REFR VIEN, P785
  • [16] The compression/absorption heat pump cycle -: conceptual design improvements and comparisons with the compression cycle (Reprinted)
    Hultén, M
    Berntsson, T
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2002, 25 (04): : 487 - 497
  • [17] Jackson B.W., 1964, Chemical Engineering Progress, V60, P62
  • [18] Kang YT, 2000, INT J REFRIG, V23, P430
  • [19] Experimental study of operating characteristics of compression/absorption high-temperature hybrid heat pump using waste heat
    Kim, Jiyoung
    Park, SeonZyong
    Baik, Young-Jin
    Chang, Ki-Chang
    Ra, Ho-Sang
    Kim, Minsung
    Kim, Yongchan
    [J]. RENEWABLE ENERGY, 2013, 54 : 13 - 19
  • [20] The effect of nano-particles on the bubble absorption performance in a binary nanofluid
    Kim, JK
    Jung, JY
    Kang, YT
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2006, 29 (01): : 22 - 29