[2] Univ Moratuwa, Dept Elect Engn, Moratuwa, Sri Lanka
来源:
2020 19TH INTERNATIONAL CONFERENCE ON HARMONICS AND QUALITY OF POWER (ICHQP)
|
2020年
关键词:
Voltage unbalance;
emission assessment;
sensitivity analysis;
transfer coefficient;
EMISSION ASSESSMENT;
D O I:
10.1109/ichqp46026.2020.9177931
中图分类号:
TE [石油、天然气工业];
TK [能源与动力工程];
学科分类号:
0807 ;
0820 ;
摘要:
Voltage unbalance (VU) emission assessment is a challenging task due to the complex interactions between the sources of voltage unbalance. Consequently, to account for transferred voltage unbalance from neighbouring busbars, IEC/TR 61000-3-13 has introduced influence and transfer coefficients in the VU allocation and emission assessment process. However, no generalised practical approaches exist to evaluate these coefficients where as IEC guidelines suggest some approximations based on simulations and field measurements. As an alternative, this paper proposes a sensitivity analysis of network VU to unbalanced installations that can be employed in VU emission assessment. The proposed methodology uses readily available inputs and utilises a linearised approach to determine the network wide sensitivity of VU to unbalanced installations which makes it feasible for practical implementation.
引用
收藏
页数:6
相关论文
共 11 条
[1]
[Anonymous], 2011, Tech. Rep.
[2]
International Electrotechnical Commission, 2012, 61000313 IECTR