Multi-Frequency bands based Pole-to-Ground fault detection method for MMC-Based radial DC distribution systems

被引:8
作者
Yang, Changqing [1 ]
Lin, Shuyue [1 ]
Guo, Moufa [1 ]
机构
[1] Fuzhou Univ, Elect Engn & Automation Coll, Fuzhou 350108, Peoples R China
基金
中国国家自然科学基金;
关键词
Faulty feeder detection; Multi-frequency bands; Pole-to-ground fault; Radial DC distribution systems; Transient zero-mode current; TRANSIENT HIGH-FREQUENCY; PROTECTION SCHEME; LOCATION METHOD; ALGORITHM;
D O I
10.1016/j.ijepes.2022.108250
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In a small-current grounding system, the pole-to-ground fault may cause the voltage drop in the fault pole and the voltage rise in the other poles. In flexible DC distribution systems, Severe voltage variation may shorten the insulation lifetime of the equipment, which leads to great concerns on the safety issue. In addition, the existence of high transition resistance degrades the accuracy of fault detection methods, thus further affecting the reliability of the system. Therefore, it is essential to explore an advanced technology for faulty feeder detection. This study proposes a faulty feeder detection method based on the characteristics of transient zero-mode current (TZMC) in multi-frequency bands. The change rate of zero-mode voltage is applied as the protection activation criterion. Then, the characteristic matrix is constructed via computing the fuzzy entropy of TZMC in each frequency band. Finally, the faulty feeder can be identified by conducting fuzzy C-means on the characteristic matrix. This proposed method is tested through simulations on the PSCAD/EMTDC platform, which successfully demonstrates its outstanding adaptability, reliability, and accuracy.
引用
收藏
页数:11
相关论文
共 30 条
  • [1] [毕天姝 Bi Tianshu], 2016, [电网技术, Power System Technology], V40, P689
  • [2] Random sampling applied to the measurement of a DC signal immersed in noise
    Carrica, D
    Benedetti, M
    Petrocelli, R
    [J]. IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2001, 50 (05) : 1319 - 1323
  • [3] Intelligent Protection of CSC-HVDC Lines Based on Moving Average and Maximum Coordinate Difference Criteria
    Farshad, Mohammad
    Karimi, Mazaher
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2021, 199
  • [4] A Novel Fault Location Method and Algorithm for DC Distribution Protection
    Feng, Xianyong
    Qi, Li
    Pan, Jiuping
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2017, 53 (03) : 1834 - 1840
  • [5] Fault section locating method and recovery strategy of pole-to-ground fault for medium voltage direct current (MVDC) distribution network
    He, Shan
    Zou, Guibin
    Sun, Chenjun
    Liu, Shiming
    [J]. JOURNAL OF ENGINEERING-JOE, 2019, (16): : 668 - 673
  • [6] Artificial intelligence-based short-circuit fault identifier for MT-HVDC systems
    Hossam-Eldin, Ahmed
    Lotfy, Ahmed
    Elgamal, Mohammed
    Ebeed, Mohammed
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (10) : 2436 - 2443
  • [7] Transient High-Frequency Impedance Comparison-Based Protection for Flexible DC Distribution Systems
    Jia, Ke
    Xuan, Zhenwen
    Feng, Tao
    Wang, Congbo
    Bi, Tianshu
    Thomas, David W. P.
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2020, 11 (01) : 323 - 333
  • [8] Transient Current Waveform Similarity Based Protection for Flexible DC Distribution System
    Jia, Ke
    Wang, Congbo
    Bi, Tianshu
    Zhu, Rui
    Xuan, Zhenwen
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2019, 66 (12) : 9301 - 9311
  • [9] [贾勇勇 Jia Yongyong], 2020, [电力系统自动化, Automation of Electric Power Systems], V44, P166
  • [10] Study on the Charge Transfer Criterion for the Pole-to-Ground Fault in DC Distribution Networks
    Li, Botong
    Ren, Xiang
    Li, Bin
    [J]. IEEE ACCESS, 2019, 7 : 102386 - 102396