Indoor environmental quality of classrooms in Southern European climate

被引:85
作者
Almeida, Ricardo M. S. F. [1 ,2 ]
de Freitas, Vasco Peixoto [2 ]
机构
[1] Sch Technol & Management, Polytech Inst Viseu, Dept Civil Engn, P-3504510 Viseu, Portugal
[2] Univ Porto, Fac Engn, Dept Civil Engn, Lab Bldg Phys, P-4200465 Oporto, Portugal
关键词
Carbon dioxide concentration; Indoor environmental quality; Relative humidity; School building retrofit; Temperature; Ventilation rates; CARBON-DIOXIDE CONCENTRATION; AIR-QUALITY; VENTILATION RATES; THERMAL COMFORT; HEALTH SYMPTOMS; SCHOOLS; PERFORMANCE; ENERGY; IMPACT; CO2;
D O I
10.1016/j.enbuild.2014.06.020
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The indoor environmental quality within a classroom is linked to the health, comfort and performance of students. It is well established that there are classroom environments where indoor environmental quality is poor. Therefore, the rehabilitation of school buildings is assumed as an appropriate strategy. Consequently, some countries have sponsored nationwide programs for the rehabilitation of school buildings, whose result has been, in some cases, other than the expected. Classrooms performance in service conditions must be evaluated and, from the results, optimized solutions should be established and carefully designed and executed to have the desired effect. Thus, a research project was defined, aiming to assess the impact of retrofit on the indoor environmental quality of school buildings. The methodology used included the in situ measurement of temperature, relative humidity, carbon dioxide concentration and ventilation rates. A total of 24 classrooms of 9 school buildings (2 non-retrofitted and 7 recently retrofitted) were studied. A long term monitoring was defined with three measurement campaigns: winter, mid-season and summer conditions, each with three weeks length. The results confirmed that non-retrofitted schools need to improve their indoor environmental conditions and in retrofitted buildings mechanical ventilation systems are not being used, with important consequences on the indoor air quality. (C) 2014 Elsevier B.V. All rights reserved.
引用
收藏
页码:127 / 140
页数:14
相关论文
共 45 条
  • [1] Impact of ventilation modes on carbon dioxide concentration levels in Kuwait classrooms
    Al-Rashidi, Khaled
    Loveday, Dennis
    Al-Mutawa, Nawaf
    [J]. ENERGY AND BUILDINGS, 2012, 47 : 540 - 549
  • [2] Alfano FRd'Ambrosio, 2010, INDOOR ENV ENERGY 1
  • [3] Almeida R., 2010, 1 CENTR EUR S BUILD
  • [4] American Society of Heating, 2013, 6212013 ASHRAE
  • [5] [Anonymous], 2018, Standard Guide for Using Indoor Carbon Dioxide Concentrations to Evaluate Indoor Air Quality and Ventilation, DOI DOI 10.1520/D6245-18
  • [6] [Anonymous], 15251 CEN EUR COMM S
  • [7] [Anonymous], 2013, ASHRAE Standard 55 - 2013
  • [8] [Anonymous], 2000, 38. International Organization of Standardization, "Earth-moving Machinery - Laboratory Evaluation of Operator Seat Vibration", ISO 7096, 2000.
  • [9] ASTM, 2011, E741 ASTM
  • [10] Awbi H.B., 2003, Ventilation of Buildings