Correlation of two-phase friction for refrigerants in small-diameter tubes

被引:304
作者
Zhang, M
Webb, RL
机构
[1] Penn State Univ, Coll Engn, Dept Engn Mech, University Pk, PA 16802 USA
[2] Thermo King Corp, Minneapolis, MN 55420 USA
关键词
two-phase; pressure drop; correlation; refrigerant; micro-channel;
D O I
10.1016/S0894-1777(01)00066-8
中图分类号
O414.1 [热力学];
学科分类号
摘要
Single-phase and adiabatic two-phase flow pressure drop were measured for R-134A, R-22 and R-404A flowing in a multi-port extruded aluminum tube with hydraulic diameter of 2.13 mm, and in two copper tubes having inside diameters of 6.25 and 3.25 mm, respectively. The single-phase friction factor was predicted within +/-10% using the Blasius friction correlation. The Friedel correlation did not predict the two-phase data accurately, especially for high reduced pressure. Using the data taken in the present and in a previous study, a new correlation for two-phase friction pressure drop in small diameter tubes was developed by modifying the Friedel correlation. The new correlation predicts 119 data points with a mean deviation of 11.5%. (C) 2001 Elsevier Science Inc. All rights reserved.
引用
收藏
页码:131 / 139
页数:9
相关论文
共 23 条
[1]  
Baroczy C.J., 1966, Chem Eng Progr Symp Ser, V62, P232
[2]   Pressure drop of pure HFC refrigerants and their mixtures flowing in capillary tubes [J].
Chang, SD ;
Ro, ST .
INTERNATIONAL JOURNAL OF MULTIPHASE FLOW, 1996, 22 (03) :551-561
[4]  
CHISHOLM D, 1970, P I MECH ENG, V184, P24
[5]  
Chisholm D., 1983, Two-Phase Flow in Pipelines and Heat Exchangers
[6]  
Collier J., 1994, Convection Boiling and Condensation, V3rd
[7]  
Friedel L., 1979, EUROPEAN 2 PHASE FLO
[8]  
Hirofumi H., 1995, Condensation in Extruded Aluminum Tubes
[9]  
Holman J.P., 1989, EXPT METHODS ENG, V5th
[10]  
LOCKHART RW, 1949, CHEM ENG PROG, V45, P39