Numerical modeling and performance analysis of a membrane-based air dehumidifier using ionic liquid desiccant

被引:9
作者
Liu, Xiaoli [1 ]
Qu, Ming [1 ]
Liu, Xiaobing [2 ]
Wang, Lingshi [2 ]
Warner, Joseph [2 ]
Gao, Zhiming [2 ]
机构
[1] Purdue Univ, Lyles Sch Civil Engn, Civil Engn Bldg,550 Stadium Mall Dr, W Lafayette, IN 47907 USA
[2] Oak Ridge Natl Lab, Oak Ridge, TN USA
关键词
Numerical modeling; Membrane; Ionic liquid desiccant; Air dehumidifier; MASS EXCHANGER; RELATIVE-HUMIDITY; HEAT; FLOW; SYSTEM; CONTACTOR; SINGLE;
D O I
10.1016/j.applthermaleng.2020.115754
中图分类号
O414.1 [热力学];
学科分类号
摘要
Membrane-based Liquid Desiccant Air Dehumidifier (MLDAD) has the potential to overcome the shortcomings of the conventional open-tower liquid desiccant air dehumidifier. The MLDAD uses membranes with high water vapor permeability to separate air stream from the liquid desiccant and thus eliminates carry-over and the resulting corrosion issues. Recently, the ionic liquid desiccant becomes a promising alternative to conventional liquid desiccant. The ionic liquid desiccant has a large potential of dehumidification, which is also non-corrosive to metals and non-crystallizable. A two-dimensional numerical heat and mass transfer model of the MLDAD using a recently identified ionic liquid desiccant, [EMIM]OAc, is presented in this paper. This model can simulate the performance of the MLDAD with various designs, including different selections of liquid desiccant and membrane materials, dimensions of the MLDAD, and flow patterns. For porous membranes, this model accounts for several micro-scale mass transfer mechanisms of vapor transportation across the membrane. It can also model the mass transfer performance of dehumidifiers using non-porous membranes based on the experimentally measured membrane permeance. The numerical model was validated against the performance data available from literature and experimental tests. The maximum discrepancy of the latent effectiveness between the measured and the model-predicted results was about 6% when porous membranes were used. A parametric study was conducted with the numerical model. The results indicated that the membrane permeability, air path height, and solution to air mass ratio were the most critical parameters, determining the dehumidification performance of the MLDAD.
引用
收藏
页数:16
相关论文
共 50 条
  • [41] Performance analysis of a novel frost-free air-source heat pump with integrated membrane-based liquid desiccant dehumidification and humidification
    Su, Wei
    Zhang, Xiaosong
    ENERGY AND BUILDINGS, 2017, 145 : 293 - 303
  • [42] Multi-stage internally-cooled membrane-based liquid desiccant dehumidifiers: Driving-force based insights into structural improvement
    Fang, Song
    Zhou, Xia
    Rong, Yangyiming
    Zhi, Xiaoqin
    Wang, Kai
    Qiu, Limin
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2021, 171
  • [43] Hollow fibre membrane-based liquid desiccant humidity control for controlled environment agriculture
    Lefers, Ryan M.
    Bettahalli, N. M. Srivatsa
    Fedoroff, Nina, V
    Ghaffour, Noreddine
    Davies, Philip A.
    Nunes, Suzana P.
    Leiknes, TorOve
    BIOSYSTEMS ENGINEERING, 2019, 183 : 47 - 57
  • [44] Liquid desiccant dehumidifier: Development of a new performance predication model based on CFD
    Luo, Yimo
    Yang, Hongxing
    Lu, Lin
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2014, 69 : 408 - 416
  • [45] Performance prediction of a liquid desiccant dehumidifier using artificial neural networks approach
    Bouzeffour, Fatih
    Khelidj, Benyoucef
    Yahi, Ferhat
    Belkacemi, Djelloul
    Taane, Walid
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2020, 27 (02) : 211 - 225
  • [46] Membrane-based packed-sheet liquid desiccant dehumidification system
    Elsafi, Amin M.
    Bahrami, Majid
    APPLIED THERMAL ENGINEERING, 2024, 236
  • [47] Numerical study on the moisture transfer characteristics of membrane-based liquid desiccant dehumidifiers: Resistance distribution and concentration polarization
    Fang, Song
    Zhi, Xiaoqin
    Cheng, Xingwang
    Qiu, Limin
    Wang, Kai
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2020, 155
  • [48] On the in-depth scaling and dimensional analysis of a cross-flow membrane liquid desiccant dehumidifier
    Lin, Jie
    Huang, Si-Min
    Wang, Ruzhu
    Chua, Kian Jon
    APPLIED ENERGY, 2019, 250 : 786 - 800
  • [49] Adaption of an Evaporative Desert Cooler into a Liquid Desiccant Air Conditioner: Experimental and Numerical Analysis
    Jaradat, Mustafa
    Al-Addous, Mohammad
    Albatayneh, Aiman
    ATMOSPHERE, 2020, 11 (01)
  • [50] Experimental analysis of dehumidification performance of an evaporative cooling-assisted internally cooled liquid desiccant dehumidifier
    Park, Joon-Young
    Kim, Beom-Jun
    Yoon, Soo-Yeol
    Byon, Yoo-Suk
    Jeong, Jae-Weon
    APPLIED ENERGY, 2019, 235 : 177 - 185