Numerical modeling and performance analysis of a membrane-based air dehumidifier using ionic liquid desiccant

被引:9
|
作者
Liu, Xiaoli [1 ]
Qu, Ming [1 ]
Liu, Xiaobing [2 ]
Wang, Lingshi [2 ]
Warner, Joseph [2 ]
Gao, Zhiming [2 ]
机构
[1] Purdue Univ, Lyles Sch Civil Engn, Civil Engn Bldg,550 Stadium Mall Dr, W Lafayette, IN 47907 USA
[2] Oak Ridge Natl Lab, Oak Ridge, TN USA
关键词
Numerical modeling; Membrane; Ionic liquid desiccant; Air dehumidifier; MASS EXCHANGER; RELATIVE-HUMIDITY; HEAT; FLOW; SYSTEM; CONTACTOR; SINGLE;
D O I
10.1016/j.applthermaleng.2020.115754
中图分类号
O414.1 [热力学];
学科分类号
摘要
Membrane-based Liquid Desiccant Air Dehumidifier (MLDAD) has the potential to overcome the shortcomings of the conventional open-tower liquid desiccant air dehumidifier. The MLDAD uses membranes with high water vapor permeability to separate air stream from the liquid desiccant and thus eliminates carry-over and the resulting corrosion issues. Recently, the ionic liquid desiccant becomes a promising alternative to conventional liquid desiccant. The ionic liquid desiccant has a large potential of dehumidification, which is also non-corrosive to metals and non-crystallizable. A two-dimensional numerical heat and mass transfer model of the MLDAD using a recently identified ionic liquid desiccant, [EMIM]OAc, is presented in this paper. This model can simulate the performance of the MLDAD with various designs, including different selections of liquid desiccant and membrane materials, dimensions of the MLDAD, and flow patterns. For porous membranes, this model accounts for several micro-scale mass transfer mechanisms of vapor transportation across the membrane. It can also model the mass transfer performance of dehumidifiers using non-porous membranes based on the experimentally measured membrane permeance. The numerical model was validated against the performance data available from literature and experimental tests. The maximum discrepancy of the latent effectiveness between the measured and the model-predicted results was about 6% when porous membranes were used. A parametric study was conducted with the numerical model. The results indicated that the membrane permeability, air path height, and solution to air mass ratio were the most critical parameters, determining the dehumidification performance of the MLDAD.
引用
收藏
页数:16
相关论文
共 50 条
  • [21] Experimental investigation and performance analysis of a spray-type ionic liquid desiccant dehumidifier
    Liang, Jyun-De
    Kao, Chia-Lin
    Chen, Chih-Hao
    Ho, Hong-Yi
    Huang, Chih-Hsueh
    Chen, Sih-Li
    APPLIED THERMAL ENGINEERING, 2024, 254
  • [22] Experimental Investigation on a Novel Air Dehumidifier Using Liquid Desiccant
    Qiu, G. Q.
    Riffat, S. B.
    INTERNATIONAL JOURNAL OF GREEN ENERGY, 2010, 7 (02) : 174 - 180
  • [23] Performance analysis of different flow types of internally-cooled membrane-based liquid desiccant dehumidifiers
    Li, Wei
    Yao, Ye
    ENERGY, 2021, 228
  • [24] Performance testing of a cross-flow membrane-based liquid desiccant dehumidification system
    Bai, Hongyu
    Zhu, Jie
    Chen, Ziwei
    Ma, Lina
    Wang, Ruzhu
    Li, Tingxian
    APPLIED THERMAL ENGINEERING, 2017, 119 : 119 - 131
  • [25] Modeling and performance analysis of solar air pretreatment collector/regenerator using liquid desiccant
    Peng, Donggen
    Zhang, Xiaosong
    RENEWABLE ENERGY, 2009, 34 (03) : 699 - 705
  • [26] The design and experimental investigation of membrane-based tubular liquid desiccant dehumidification system
    Kavasogullari, Baris
    Cihan, Ertugrul
    Demir, Hasan
    PAMUKKALE UNIVERSITY JOURNAL OF ENGINEERING SCIENCES-PAMUKKALE UNIVERSITESI MUHENDISLIK BILIMLERI DERGISI, 2023, 29 (04): : 303 - 313
  • [27] PERFORMANCE ANALYSIS ON THE INTERNALLY COOLED DEHUMIDIFIER USING TWO LIQUID DESICCANT SOLUTIONS
    Koronaki, I. P.
    Christodoulaki, R. I.
    Papaefthimiou, V. D.
    Rogdakis, E. D.
    PROCEEDINGS OF THE ASME 11TH BIENNIAL CONFERENCE ON ENGINEERING SYSTEMS DESIGN AND ANALYSIS, 2012, VOL 2, 2012, : 627 - 638
  • [28] Analysis of parallel flow type internally cooled membrane based liquid desiccant dehumidifier using neural networks approach
    Quadros, Jaimon Dennis
    Khan, S. A.
    Prashanth, T.
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2022, 28 (03) : 403 - 421
  • [29] Performance evaluation of a membrane-based flat-plate heat and mass exchanger used for liquid desiccant regeneration
    Bai, Hongyu
    Zhu, Jie
    Chen, Ziwei
    Chu, Junze
    Liu, Yiwen
    APPLIED THERMAL ENGINEERING, 2018, 139 : 569 - 584
  • [30] Performance analysis of a multistage internal circulation liquid desiccant dehumidifier
    Cheng, Xingwang
    Rong, Yangyiming
    Zhou, Xia
    Gu, Chenjie
    Zhi, Xiaoqin
    Qiu, Limin
    Yuan, Yijun
    Wang, Kai
    APPLIED THERMAL ENGINEERING, 2020, 172