Climatic applicability of downdraught evaporative cooling in the United States of America

被引:13
|
作者
Aparicio-Ruiz, Pablo [1 ]
Schiano-Phan, Rosa [2 ]
Manuel Salmeron-Lissen, Jose [3 ]
机构
[1] Univ Seville, Escuela Tecn Super Ingn, Grp Ingn Org, Camino Descubrimientos S-N, Seville 41092, Spain
[2] Univ Westminster, FABE, Dept Architecture, 35 Marylebone Rd, London NW1 5LS, England
[3] Univ Seville, Escuela Tecn Super Ingn, Grp Termotecnia, Camino Descubrimientos S-N, Seville 41092, Spain
关键词
Climatic applicability; Downdraught cooling; Dry bulb temperature; Passive downdraught evaporative cooling; Wet bulb temperature; CLASSIFICATION;
D O I
10.1016/j.buildenv.2018.03.039
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The potential for application of downdraught cooling in the United States of America (U.S.) depends on its climatic characteristics. However, due to the large geographic span of the country, it varies due to differences in latitude, and a range of geographic features influencing climate, including altitude, topography and terrain. This study describes the development of climatic applicability maps of downdraught cooling in the U.S., which can aid designers in the initial identification of the correct cooling strategy for the geographic area of interest. The proposed approach is based on a set of maps, which are derived from two related climatic indexes: dry bulb temperature to wet bulb temperature depression (DBT - WBT), representing the climatic opportunity, and 26 degrees C minus wet bulb temperature (26 degrees C - WBT), representing the climatic opportunity against the theoretical cooling requirement for each location. The downdraught cooling strategy and degree of applicability is classified in the map, based on the aforementioned climatic and cooling parameters. Finally, four representative buildings in four different regions with different climatic conditions were selected for climatic analysis. This resulted in the identification of some climate zones for downdraught cooling application in the U.S. and the suggestion of appropriate design strategies for each of them.
引用
收藏
页码:162 / 176
页数:15
相关论文
共 50 条
  • [1] Climatic applicability of downdraught cooling in Europe
    Manuel Salmeron, Jose
    Jose Sanchez, Francisco
    Sanchez, Jose
    Alvarez, Servando
    Luis Molina, Jose
    Salmeron, Rafael
    ARCHITECTURAL SCIENCE REVIEW, 2012, 55 (04) : 259 - 272
  • [2] Climatic applicability of downdraught cooling in China
    Xuan, Huang
    Ford, Brian
    ARCHITECTURAL SCIENCE REVIEW, 2012, 55 (04) : 273 - 286
  • [3] Geo-climatic applicability of evaporative and ventilative cooling in China
    Chiesa, Giacomo
    INTERNATIONAL JOURNAL OF VENTILATION, 2016, 15 (3-4) : 205 - 219
  • [4] Passive downdraught evaporative cooling: performance in a prototype house
    Ford, Brian
    Wilson, Robin
    Gillott, Mark
    Ibraheem, Omar
    Salmeron, Jose
    Jose Sanchez, Francisco
    BUILDING RESEARCH AND INFORMATION, 2012, 40 (03): : 290 - 304
  • [5] Climatic applicability of indirect evaporative cooling strategies for data centers in China
    Cui, Xin
    Yang, Chuanjun
    Yan, Weichao
    Wang, Xinyu
    Liu, Yahui
    Jin, Liwen
    JOURNAL OF BUILDING ENGINEERING, 2024, 83
  • [6] Passive downdraught evaporative cooling - II. Airflow modelling
    Cook, MJ
    Robinson, D
    Lomas, KJ
    Bowman, NT
    Eppel, H
    INDOOR AND BUILT ENVIRONMENT, 2000, 9 (06) : 325 - 334
  • [7] Integrating a passive downdraught evaporative cooling tower into a Saudi house-The impact of climatic conditions on PDEC performance
    Alshenaifi, Mohammad A.
    Sharples, Steve
    Abuhussain, Mohammed A.
    Alotaibi, Badr S.
    Aldersoni, Ali A.
    Abdelhafez, Mohamed H. H.
    BUILDING AND ENVIRONMENT, 2023, 242
  • [8] Passive downdraught evaporative cooling - I. Concept and precedents
    Bowman, NT
    Eppel, H
    Lomas, KJ
    Robinson, D
    Cook, MJ
    INDOOR AND BUILT ENVIRONMENT, 2000, 9 (05) : 284 - 290
  • [9] Analysis of passive downdraught evaporative cooling windcatcher for greenhouses in hot climatic conditions: Parametric study and impact of neighbouring structures
    Ghoulem, Marouen
    El Moueddeb, Khaled
    Nehdi, Ezzedine
    Zhong, Fangliang
    Calautit, John
    BIOSYSTEMS ENGINEERING, 2020, 197 : 105 - 121
  • [10] Applicability of Active Downdraught Cooling in Hot and Humid Climate in China
    Xuan, Huang
    Lian, Zhiwei
    Ford, Brian
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 1905 - 1912