Pressurized adsorption cooling cycles driven by solar/waste heat

被引:19
作者
Bin Ismail, Azhar [1 ]
Li, Ang [1 ]
Thu, Kyaw [1 ]
Ng, Kim Choon [1 ]
Chun, Wongee [2 ]
机构
[1] Natl Univ Singapore, Dept Mech Engn, Singapore 117576, Singapore
[2] Jeju Natl Univ, Dept Nucl & Energy, Cheju, South Korea
关键词
Adsorption; Single-stage; Thermal activation; INTERNATIONAL STANDARD FORMULATION; THERMODYNAMIC PROPERTIES; PERFORMANCE EVALUATION; WASTE HEAT; REFRIGERATION CYCLES; ACTIVATED CARBONS; SOLAR-ENERGY; TEMPERATURES; CHILLER; STATE;
D O I
10.1016/j.applthermaleng.2014.02.063
中图分类号
O414.1 [热力学];
学科分类号
摘要
This article presents the performance analysis of single-stage two bed adsorption refrigeration cycles working at pressurized conditions. Four specimens of activated carbon adsorbent and refrigerant pairs, which are Maxsorb III with Propane, n-butane, HFC-134a, R-32, and R507a are studied. The relationships between equilibrium pressures, adsorbent temperatures and equilibrium adsorption concentrations (Daring diagram) are presented. Parametric analyses have been carried by varying the regeneration, cooling water and evaporation temperatures. Theoretical analysis for these adsorption cycles working pairs shows that the choice of refrigerants amongst these pairs depends on the operational requirements and conditions. The authors thus present in a graphical representation of the choice based on these requirements. At higher required chilling temperatures and lower ambient temperatures, R-32 is preferred with higher specific cooling capacities. When lower temperature cooling is required while the ambient temperature is high, Propane is preferred. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:106 / 113
页数:8
相关论文
共 42 条
[31]   Thermodynamic tools for chiller diagnostics and optimization [J].
Ng, KC .
HEAT TRANSFER ENGINEERING, 2004, 25 (08) :1-4
[32]  
Otowa T., 1993, GAS SEP PURIF, V7, P241, DOI DOI 10.1016/0950-4214(93)80024-Q
[33]  
PREBEG Z, 2000, J THEOR, V2, P2000
[34]   Performance evaluation of a low-temperature waste heat driven multi-bed adsorption chiller [J].
Saha, BB ;
Koyama, S ;
Lee, JB ;
Kuwahara, K ;
Alam, KCA ;
Hamamoto, Y ;
Akisawa, A ;
Kashiwagi, T .
INTERNATIONAL JOURNAL OF MULTIPHASE FLOW, 2003, 29 (08) :1249-1263
[35]  
SAHA BB, 2011, 2 EUR C POLYG
[36]   Selection and further activation of activated carbons for removal of nitrogen species in gas oil as a pretreatment for its deep hydrodesulfurization [J].
Sano, Y ;
Choi, KH ;
Korai, Y ;
Mochida, I .
ENERGY & FUELS, 2004, 18 (03) :644-651
[37]  
SANO Y, 2003, PAPERS AM CHEM SOC
[38]  
STANDARD ARI, 2000, ABSORPTION WATER CHI, P560
[39]   An international standard equation of state for difluoromethane (R-32) for temperatures from the triple point at 136.34 K to 435 K and pressures up to 70 MPa [J].
TillnerRoth, R ;
Yokozeki, A .
JOURNAL OF PHYSICAL AND CHEMICAL REFERENCE DATA, 1997, 26 (06) :1273-1328
[40]   AN INTERNATIONAL STANDARD FORMULATION FOR THE THERMODYNAMIC PROPERTIES OF 1,1,1,2-TETRAFLUROETHANE (HFC-134A) FOR TEMPERATURES FROM 170-K TO 455-K AND PRESSURES UP TO 70-MPA [J].
TILLNERROTH, R ;
BAEHR, HD .
JOURNAL OF PHYSICAL AND CHEMICAL REFERENCE DATA, 1994, 23 (05) :657-729