An experimental study on a novel direct expansion based temperature and humidity independent control air conditioning system

被引:7
作者
Chen, Wenjing [1 ]
Fang, Guanyu [1 ]
Wang, Caixia [1 ]
Weng, Wenbing [2 ]
Chan, Ming-yin [1 ]
Deng, Shiming [1 ]
Liu, Xuefeng [3 ]
Yan, Huaxia [4 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hung Hom, Kowloon, Hong Kong 999077, Peoples R China
[2] Univ Shanghai Sci & Technol, Sch Environm & Architecture, Gungong RD, Shanghai 20082, Peoples R China
[3] South China Univ Technol, Sch Elect Power, Wushan RD, Guangzhou 510641, Guangdong, Peoples R China
[4] Technol & Higher Educ Inst Hong Kong, Fac Sci & Technol, Hong Kong, Peoples R China
来源
INNOVATIVE SOLUTIONS FOR ENERGY TRANSITIONS | 2019年 / 158卷
基金
中国国家自然科学基金;
关键词
Direct expansion; Temperature and humidity control; Decouple; Air-condtioning system; INHERENT OPERATIONAL CHARACTERISTICS; EQUIPMENT;
D O I
10.1016/j.egypro.2019.01.172
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Direct expansion (DX) air conditioning (A/C) system are widely used in various buildings because they are simpler and more energy efficient, and generally cost less to own and maintain. However, it is often problematical for a conventional On -Off controlled DX A/C system to simultaneously control indoor temperature and humidity, since the cooling and dehumidification process of air are highly coupled, unless costly extra equipment or complicated control method to decouple the cooling and dehumidification are provided. Therefore, a novel DX based temperature and humidity independent control air conditioning (DX-THIC) system with two parallel -connected condensers and two electronic expansion valves is presented for improved indoor environmental control and energy efficiency. This paper reports on an experimental study on the operating performances of a prototype experimental DX-THIC system. The experimental results demonstrated that the proposed DX-THIC system can provide independent control of indoor temperature and humidity. The experimental results also demonstrated that the indoor air humidity could influence the operating performances of the DX-THIC system. (C) 2019 The Authors. Published by Elsevier Ltd.
引用
收藏
页码:2237 / 2243
页数:7
相关论文
共 11 条
[1]   Development of a steady-state physical-based mathematical model for a direct expansion based enhanced dehumidification air conditioning system [J].
Chen, Wenjing ;
Chan, Ming-yin ;
Weng, Wenbing ;
Yan, Huaxia ;
Deng, Shiming .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2018, 91 :55-68
[2]   An experimental study on the operational characteristics of a direct expansion based enhanced dehumidification air conditioning system [J].
Chen, Wenjing ;
Chan, Ming-yin ;
Weng, Wenbing ;
Yan, Huaxia ;
Deng, Shiming .
APPLIED ENERGY, 2018, 225 :922-933
[3]   A direct expansion based enhanced dehumidification air conditioning system for improved year-round indoor humidity control in hot and humid climates [J].
Chen, Wenjing ;
Chan, Ming-yin ;
Deng, Shiming ;
Yan, Huaxia ;
Weng, Wenbing .
BUILDING AND ENVIRONMENT, 2018, 139 :95-109
[4]   A simulation study for evaluating the performances of different types of house-hold radiant air conditioning systems [J].
Li Zhao ;
Chen Jianbo ;
Wang Fei ;
Cui Lingchuang ;
Qu Minglu .
APPLIED THERMAL ENGINEERING, 2018, 131 :553-564
[5]   Further study on the inherent operating characteristics of a variable speed direct expansion air conditioning system [J].
Li, Zhao ;
Xu, Xiangguo ;
Deng, Shiming ;
Pan, Dongmei .
APPLIED THERMAL ENGINEERING, 2014, 66 (1-2) :206-215
[6]   An experimental study on the inherent operational characteristics of a direct expansion (DX) air conditioning (A/C) unit [J].
Li, Zheng ;
Deng, Shiming .
BUILDING AND ENVIRONMENT, 2007, 42 (01) :1-10
[7]   Comfortable, high-efficiency heat pump with desiccant-coated, water-sorbing heat exchangers [J].
Tu, Y. D. ;
Wang, R. Z. ;
Ge, T. S. ;
Zheng, X. .
SCIENTIFIC REPORTS, 2017, 7
[8]   Inherent operational characteristics and operational stability of a variable speed direct expansion air conditioning system [J].
Xia, Yudong ;
Deng, Shiming ;
Chan, Ming-Yin .
APPLIED THERMAL ENGINEERING, 2017, 113 :268-277
[9]   A review on temperature and humidity control methods focusing on air-conditioning equipment and control algorithms applied in small-to-medium-sized buildings [J].
Xu, Xiangguo ;
Zhong, Ziwen ;
Deng, Shiming ;
Zhang, Xiaobo .
ENERGY AND BUILDINGS, 2018, 162 :163-176
[10]   Inherent correlation between the total output cooling capacity and equipment sensible heat ratio of a direct expansion air conditioning system under variable-speed operation (XXG SMD SHR DX AC unit) [J].
Xu, Xiangguo ;
Xia, Liang ;
Chan, Mingyin ;
Deng, Shiming .
APPLIED THERMAL ENGINEERING, 2010, 30 (13) :1601-1607