Air-side performance evaluation of three types of heat exchangers in dry, wet and periodic frosting conditions

被引:57
作者
Zhang, Ping [1 ,2 ]
Hrnjak, P. S. [1 ]
机构
[1] Univ Illinois, Dept Engn Sci & Mech, Urbana, IL 61801 USA
[2] Zhejiang Vocat Coll Commerce, Hangzhou, Zhejiang, Peoples R China
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2009年 / 32卷 / 05期
关键词
Air conditioning; Heat exchanger; Air chiller; Finned tube; Geometry; Measurement; Heat transfer; Pressure drop; Water retention; Comparison;
D O I
10.1016/j.ijrefrig.2008.11.006
中图分类号
O414.1 [热力学];
学科分类号
摘要
The performances of three types of heat exchangers that use the louver fin geometry: (1) parallel flow parallel fin with extruded flat tubes heat exchanger (PF2), (2) parallel flow serpentine fin with extruded flat tubes heat exchanger (PFSF) and (3) round tube wave plate fin heat exchanger (RTPF) have been experimentally studied under dry, wet and frost conditions and results are presented. The parameters quantified include air-side pressure drop, water retention on the surface of the heat exchanger, capacity and overall heat transfer coefficient for air face velocity 0.9, 2 and 3 m/s, air humidity 70% and 80% and different orientations. The performances of three types of heat exchanger are compared and the results obtained are presented. The condensate drainage behavior of the air-side surface of these three heat exchanger types was studied using both the dip testing method and wind tunnel experiment. (C) 2008 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:911 / 921
页数:11
相关论文
共 10 条
[1]   HEAT-TRANSFER AND PRESSURE-DROP CHARACTERISTICS OF FLAT TUBE AND LOUVERED PLATE FIN SURFACES [J].
ACHAICHIA, A ;
COWELL, TA .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 1988, 1 (02) :147-157
[2]   AN EXPERIMENTAL-STUDY OF THE LOCAL HEAT-TRANSFER CHARACTERISTICS IN AUTOMOTIVE LOUVERED FINS [J].
AOKI, H ;
SHINAGAWA, T ;
SUGA, K .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 1989, 2 (03) :293-300
[3]   Air side performance of brazed aluminum heat exchangers [J].
Chang, YJ ;
Wang, CC .
JOURNAL OF ENHANCED HEAT TRANSFER, 1996, 3 (01) :15-28
[4]  
DAVENPORT CJ, 1980, THESIS DEP MECH ENG
[5]  
DEJONG NC, 1999, TR146 ACRC U ILL URB
[6]  
Kim M.H., 2002, INT J REFRIG, V25, P641
[7]  
KIM MH, 2000, P ASME ADV EN SYST D, V40, P47
[8]  
Sunden B., 1990, Proc. 9th International Heat Transfer Conference, P91
[9]  
WEBB RL, 1992, ASHRAE TRAN, V98, P391
[10]   Dynamic dip testing as a method to assess the condensate drainage behavior from the air-side surface of compact heat exchangers [J].
Zhong, YF ;
Joardar, A ;
Gu, ZP ;
Park, YG ;
Jacobi, AM .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2005, 29 (08) :957-970