Experimental Study on the Flashover Characteristics of Polluted Insulators under Short-tail Lightning Impulse Waveform

被引:0
作者
Xiao, Pei [1 ]
He, Hengxin [1 ]
He, Junjia [1 ]
Cheng, Chen [1 ]
Xiao, Mian [1 ]
机构
[1] Huazhong Univ Sci & Technol, State Key Lab Adv Electromagnet Engn & Technol, 1037 Luoyu Rd, Wuhan, Hubei, Peoples R China
来源
2018 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE) | 2018年
关键词
polluted insulator; equivalent salt deposit density; short-tail impulse; flashover voltage; transmission line; LOW ATMOSPHERIC-PRESSURE; PERFORMANCE;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The pollution flashover accidents of insulator strings do harm to the safe operation of transmission lines. The paper aims to investigate the flashover characteristics of a 2-unit glass suspension string under 0.5/5 mu s short-tail impulses. Firstly, in order to represent the pre-heating effect of operation voltage, a composite test circuit was established. It can generate a combined voltage waveform consists of the power frequency ac voltage and a subsequent 0.5/5 mu s impulse. Secondly, adopting the artificial contamination test method with ESDD in the range of 0.010.1mg/cm(2), in the absence of the ac voltage, the U-50% of the 2-unit glass suspension string decreases with increasing of ESDD, and reached saturation when ESDD is larger than 0.025 mg/cm(2). Comparing to the clean insulator, U-50% was reduced by 25%. Thirdly, the result of composite test indicates that the prestressed ac voltage has little influence on the U-50% of the insulator. According to the observed flashover paths, most of the flashover was happened between surface of two insulators. The potential distortion caused by the pollutant deposits layer was beneficial to streamer inception. This might be the reason rather than the formation of pre-heated dry bands that leads to a lower U-50% when the polluted insulator is subjected to short tail impulses.
引用
收藏
页数:4
相关论文
共 15 条
  • [1] Arshad Nekahi A, 2017, PROPERTIES APPL DIEL, P612
  • [2] Dhahbi-Megriche N, 2017, ICEMIS
  • [3] MULTISTORY TRANSMISSION TOWER MODEL FOR LIGHTNING SURGE ANALYSIS
    ISHII, M
    KAWAMURA, T
    KOUNO, T
    OHSAKI, E
    SHIOKAWA, K
    MUROTANI, K
    HIGUCHI, T
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (03) : 1327 - 1335
  • [4] Study of AC Pollution Flashover Performance of Porcelain Insulators at High Altitude Sites of 2800 ∼ 4500 m
    Jiang, Xingliang
    Zhang, Zhijin
    Yuan, Jihe
    Hu, Qin
    Luo, Liyun
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (03) : 1426 - 1432
  • [5] Modeling of altitude effects on AC flashover of polluted high voltage insulators
    Rizk, FAM
    Rezazada, AQ
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (02) : 810 - 822
  • [6] Analysis of 500 kV OHTL polluted insulator string behavior during lightning strokes
    Said, A.
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2018, 95 : 405 - 416
  • [7] Su Zhiyi, 2010, Power System Technology, V34, P124
  • [8] [宿志一 Su Zhiyi], 2003, [中国电力, Electric Power], V36, P57
  • [9] Sun Cai-xin, 2004, Electric Power, V37, P1
  • [10] Sundararajan R., 2002, IEEE T ELECTR INSUL, V28, P209