Research on Quantitative Relationship between Fire Separations and Ampacity in Underground pipe gallery Electric cabin

被引:2
作者
Wang, Jiaxu [1 ]
Liu, Xuefeng [1 ]
Li, Shu [1 ]
Fang, Guanyu [2 ]
Chen, Wenjing [2 ]
Deng, Shiming [2 ]
机构
[1] South China Univ Technol, Sch Elect Power, Wushan RD, Guangzhou 510641, Guangdong, Peoples R China
[2] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hung Hom, Kowloon, Hong Kong 999077, Peoples R China
来源
INNOVATIVE SOLUTIONS FOR ENERGY TRANSITIONS | 2019年 / 158卷
基金
中国国家自然科学基金;
关键词
Underground pipe gallery; similarity criterion; dimensionless number; fire separation; cable ampacity; VOLTAGE;
D O I
10.1016/j.egypro.2019.01.587
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In recent years, underground pipe gallery has become more and more important. Its Special working environment makes temperature monitoring and control increasingly important. paper applies heat-transfer differential equation to the cable to obtain the similarity criterion of cable temperature distribution. After calculating the electric cabin model with different fire separations, it is found that the temperature distribution of the same ampacity in different fire separations conforms to certain rules. The temperature distribution of different ampacity in the same fire separation is also regular: the ampacity rises. 5%, temperature rises by 7%. As a result, the fitting formulas of the current carrying capacity, the length of the fire separation and the location of the highest temperature were also proposed. (C) 2019 The Authors. Published by Elsevier Ltd.