DC magnetisation of transformers

被引:18
作者
Ahfock, A. [1 ]
Hewitt, A. J. [1 ]
机构
[1] Univ So Queensland, Fac Engn & Surveying, Toowoomba, Qld 4350, Australia
来源
IEE PROCEEDINGS-ELECTRIC POWER APPLICATIONS | 2006年 / 153卷 / 04期
关键词
D O I
10.1049/ip-epa:20050440
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A sufficiently high DC component in the current on the secondary side of a transformer causes distortion of the primary side current. Prediction of such distortion relies on the availability of magnetisation curves that extend deep enough into saturation. A simple test, carried out at rated voltage, is proposed which allows the magnetisation curve to be deduced from measured data. In addition, a systematic procedure has been developed to evaluate the primary-current distortion in both single- and three-phase transformers. Comparison between theoretical predictions and practical measurements are made, with reasonable agreement between the two.
引用
收藏
页码:601 / 607
页数:7
相关论文
共 16 条
[1]  
BRADLEY S, 2000, 5862 STP
[2]  
COLLINSON A, 1999, 5010 EA STP
[3]   Modeling and simulation, and their validation of three-phase transformers with three legs under DC bias [J].
Fuchs, EF ;
You, Y ;
Roesler, DJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 1999, 14 (02) :443-449
[4]  
FUCHS EF, 1991, IEEE T POWER DELIVER, V6, P174
[5]   Measureme of λ-i characteristics of asymmetric three-phase transformers and their applications [J].
Fuchs, EF ;
You, YM .
IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (04) :983-990
[6]  
GIRGIS RS, 1992, IEEE T POWER DELIVER, V17, P699
[7]   Rower quality from multiple grid-connected single-phase inverters [J].
Infield, DG ;
Onions, P ;
Simmons, AD ;
Smith, GA .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (04) :1983-1989
[8]  
Jablonski M., 1988, Electromagnetic Fields in Electrical Engineering, P101
[9]  
KHALID M, 1999, J ELECT ELECT ENG, V19, P31
[10]   35 years of studies of mixing of rubber and viscoelasticity [J].
Nakajima, N .