Experimental Study on Effectiveness of Celdek Packed Liquid Desiccant Cooling System

被引:10
作者
Kumar, Rakesh [1 ]
Asati, Arun Kumar [2 ]
机构
[1] IKG Punjab Tech Univ, Mech Engn Dept, Kapurthala Highway, Jalandhar 148107, Punjab, India
[2] Shaheed Bhagat Singh State Tech Campus Ferozepur, Mech Engn Dept, Ferozepur, Punjab, India
关键词
NATURAL DRAFT DRY; MASS-TRANSFER; AIR DEHUMIDIFIER; PERFORMANCE; HEAT; BED; TOWERS; DEHUMIDIFICATION/REGENERATION; REGENERATION; COLUMN;
D O I
10.1080/01457632.2017.1338869
中图分类号
O414.1 [热力学];
学科分类号
摘要
Dehumidifier and regenerator are the most important components in a liquid desiccant cooling system. Present paper is focused on study the effect of inlet process parameters on the effectiveness of dehumidifier and regenerator of liquid desiccant cooling system. Experimental study is performed with varying inlet process parameters; mass flow rate of air, desiccant solution flow rate, inlet air temperature, inlet solution temperature, inlet specific humidity and concentration of desiccant solution. Celdek structured pads as packing material and calcium chloride as liquid desiccant is investigated first time using counter flow of the desiccant solution and air. It is concluded from the results that the effectiveness of dehumidifier increases with solution flow rate, inlet specific humidity while decreases with increasing mass flow rate of air, inlet temperature of air and desiccant, temperature and concentration of desiccant solution. The effectiveness of regenerator increases with increasing solution flow rate and inlet desiccant concentration and it decreases with increasing inlet air temperature, air flow rate and inlet solution temperature. Present paper adds to effect of inlet specific humidity, inlet temperature of the air and solution on the effectiveness of desiccant cooling system on the past research.
引用
收藏
页码:914 / 922
页数:9
相关论文
共 28 条
[1]   Predictions of moisture removal rate and dehumidification effectiveness for structured liquid desiccant air dehumidifier [J].
Abdul-Wahab, SA ;
Zurigat, YH ;
Abu-Arabi, MK .
ENERGY, 2004, 29 (01) :19-34
[2]   Performance of a Hybrid Desiccant Cooling System in a Residential Environment [J].
Ahn, Joon ;
Kim, Jaeyul ;
Kang, Byung Ha .
HEAT TRANSFER ENGINEERING, 2016, 37 (7-8) :633-639
[3]   Evaluation of heat and mass transfer coefficients in a gauze-type structured packing air dehumidifier operating with liquid desiccant [J].
Al-Farayedhi, AA ;
Gandhidasan, P ;
Al-Mutairi, MA .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2002, 25 (03) :330-339
[4]  
Alosaimy A.S., 2013, INT J MECH MECHATRON, V13, P60
[5]   A novel method to evaluate the performance of liquid desiccant air dehumidifier system [J].
Bakhtiar, Agung ;
Rokhman, Fatkhur ;
Choi, Kwang Hwan .
ENERGY AND BUILDINGS, 2012, 44 :39-44
[6]   An experimental study of structured packing dehumidifier/regenerator operating with liquid desiccant [J].
Bassuoni, M. M. .
ENERGY, 2011, 36 (05) :2628-2638
[7]   Experimental study on dehumidification/regeneration of liquid desiccant: LiBr solution [J].
Bouzenada, S. ;
Kaabi, A. N. ;
Fraikin, L. ;
Leonard, A. .
5TH INTERNATIONAL CONFERENCE ON AMBIENT SYSTEMS, NETWORKS AND TECHNOLOGIES (ANT-2014), THE 4TH INTERNATIONAL CONFERENCE ON SUSTAINABLE ENERGY INFORMATION TECHNOLOGY (SEIT-2014), 2014, 32 :673-680
[8]   Comparison between random and structured packings for dehumidification of air by lithium chloride solutions in a packed column and their heat and mass transfer correlations [J].
Chung, TW ;
Ghosh, TK ;
Hines, AL .
INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 1996, 35 (01) :192-198
[9]  
Dow, 2003, Calcium Chloride Handbook, A Guide to Properties, Forms, Storage and Handling
[10]   Design guidelines and performance study on a structured packed liquid desiccant air-conditioning system [J].
Elsarrag, E ;
Elmagzoub, E ;
Jain, S .
HVAC&R RESEARCH, 2005, 11 (02) :319-337