Spray angle effect during spray cooling of microelectronics: Experimental measurements and comparison with inverse calculations

被引:52
作者
Li, B. Q. [1 ]
Cader, T.
Schwarzkopf, J.
Okamoto, K.
Ramaprian, B.
机构
[1] Washington State Univ, Sch Mech & Mat Engn, Pullman, WA 99164 USA
[2] Isothermal Syst Res, Liberty Lake, WA 99019 USA
基金
美国国家航空航天局;
关键词
spray cooling; inverse algorithm; the truncated singular value decomposition; discrepancy principle; spray angle effect;
D O I
10.1016/j.applthermaleng.2006.01.023
中图分类号
O414.1 [热力学];
学科分类号
摘要
An experimental and inverse computational study is presented of spray cooling of microelectronics with an emphasis on the spray angle effects on cooling performance. A thermal test chip provides the heated target, and is cooled by a single pressure swirl atomizer. Thermal readings were taken at the spray angles of 0-60 degrees, at a fixed distance of 1.4 cm from the heated die surface. An inverse heat transfer computational algorithm is developed to calculate the unknown spray cooling heat fluxes using the measured temperature data inside the die. The computational scheme is a combination of the finite element method and the truncated single value decomposition with the discrepancy principle for determining the optimal truncation threshold value. Good agreement is obtained between the experimental measurements and calculated results. For this particular system, a direct estimate using temperature readings at two adjacent points would produce incorrect heat flux results and an inverse algorithm is deemed essential if an accurate heat flux is to be obtained from the measurements. It is found that a major cause for the drop-off is the reduction in spray volumetric flux delivered to the die at the greater spray angles. (c) 2006 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1788 / 1795
页数:8
相关论文
共 20 条
[1]  
ANSARI S, 2003, P INTERPACK03 MAUI H
[2]  
Beck J.V., 1985, INVERSE HEAT CONDUCT
[3]  
CADER T, 2003, P INTERPACK03 MAUI H
[4]   Effects of spray characteristics on critical heat flux in subcooled water spray cooling [J].
Chen, RH ;
Chow, LC ;
Navedo, JE .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2002, 45 (19) :4033-4043
[5]   ANALYSIS ON FILM BOILING HEAT-TRANSFER OF IMPACTING SPRAYS [J].
DEB, S ;
YAO, SC .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1989, 32 (11) :2099-2112
[6]   CORRELATION OF SAUTER MEAN DIAMETER AND CRITICAL HEAT-FLUX FOR SPRAY COOLING OF SMALL SURFACES [J].
ESTES, KA ;
MUDAWAR, I .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1995, 38 (16) :2985-2996
[7]  
Fabbri M., 2003, P ASME 2003 INT MECH, P657
[8]  
Incropera F.P., 2002, INTRO HEAT TRANSFER
[9]  
KEARNS D, 2002, 18 IEEE SEM S
[10]  
LIU L, 1982, INT J HEAT MASS TRAN, V4, P161