On Testing the Electronic Revenue Energy Meters

被引:32
作者
Ferrero, Alessandro [1 ]
Faifer, Marco [1 ]
Salicone, Simona [1 ]
机构
[1] Politecn Milan, Dipartimento Elettrotecn, I-20133 Milan, Italy
关键词
Calibration procedure; electric energy metering; nonsinusoidal conditions; POWER QUALITY;
D O I
10.1109/TIM.2009.2016821
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Electric energy meters have always been designed to account energy under sinusoidal conditions, and therefore, the uncertainty specification outside these conditions was of little interest. This was considered acceptable when the voltage and current distortion level was low and the old well-known induction meters were used. In fact, under these conditions, the measurement errors caused by distortion did not generally penalize the customers. The present situation is, however, quite different: Distortion is not any longer negligible, particularly in low-voltage systems, and the modern electronic energy meters can be much more sensitive to distortion than the induction meters, depending on the implemented measurement algorithm. This paper briefly discusses the calibration problems raised by the electronic energy meters and proposes a new calibration procedure, fully compliant with the recent Directive of the European Parliament on the measuring instruments, and based on a synthesizer of randomly distorted signals, capable of evaluating the measurement uncertainty of the energy meters under the distorted conditions that are likely to be met in their normal operating conditions.
引用
收藏
页码:3042 / 3049
页数:8
相关论文
共 13 条
[1]   Selecting revenue meters for harmonic producing loads [J].
Arseneau, R ;
Hughes, MB .
2004 11TH INTERNATIONAL CONFERENCE ON HARMONICS AND QUALITY OF POWER, 2004, :227-231
[2]   A CALIBRATION SYSTEM FOR EVALUATING THE PERFORMANCE OF HARMONIC POWER ANALYZERS [J].
ARSENEAU, R ;
FILIPSKI, P .
IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (03) :1177-1182
[3]  
Cataliotti A., 2007, P IEEE INSTR MEAS TE, P1
[4]  
*CEER EL WORK GROU, 2005, C05QOS0103 CEER ASBL
[5]  
DAN A, 2004, P 11 ICHQP LAK PLAC, P283
[6]   Harmonic pollution metering: Theoretical considerations [J].
Davis, EJ ;
Emanuel, AE ;
Pileggi, DJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (01) :19-23
[7]   A calibration procedure for a digital instrument for electric power quality measurement [J].
Ferrero, A ;
Lazzaroni, M ;
Salicone, S .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2002, 51 (04) :716-722
[8]  
Ferrero A, 1996, EUR T ELECTR POWER, V6, P401, DOI 10.1002/etep.4450060607
[9]   On the selection of the "best" test waveform for calibrating electrical instruments under nonsinusoidal conditions [J].
Ferrero, A ;
Muscas, C .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2000, 49 (02) :382-387
[10]  
FERRERO A, 2008, P 12MTC VICT BC CAN, P83