Calibration of a sensor for an ion electric field under HVDC transmission lines

被引:2
作者
Ya, Mou [1 ]
Yu, Zhanqing [1 ]
Fan, Yazhou [2 ]
Zhang, Bo [1 ]
Zhang, Chao [2 ]
Wang, Xiaorui [1 ]
Zeng, Rong [1 ]
He, Jinliang [1 ]
机构
[1] Tsinghua Univ, Dept Elect Engn, State Key Lab Power Syst, Beijing, Peoples R China
[2] Guangdong Power Grid Co Ltd, Jiangmen Power Supply Bur, Jiangmen 529000, Peoples R China
来源
JOURNAL OF ENGINEERING-JOE | 2019年 / 16期
基金
中国国家自然科学基金;
关键词
electric sensing devices; electric field measurement; electric fields; HVDC power transmission; electromagnetic compatibility; calibration; power transmission lines; experimental device; system operation safety; equipment insulation; calibration experiments; air synthetic electric field; calibration method; differential electric field sensor; distorted field; ion currents; DC electric field; synthetic ion flow electric field; high-voltage direct-current transmission projects; HVDC transmission lines;
D O I
10.1049/joe.2018.8400
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
With the development of high-voltage direct-current (HVDC) transmission projects, the issue of electromagnetic compatibility has become more and more severe, especially the synthetic ion flow electric field. The DC electric field is inseparable from the equipment insulation, the safety of the system operation, and effects on organisms nearby. The measurement of the synthetic electric field of ion flow has been a major difficulty due to the influence of ion currents and distorted field. A differential electric field sensor for measuring the synthetic electric field is proposed. The calibration method and the experimental device for the measurement of the air synthetic electric field of ion flow are presented. Calibration experiments show that the calibration method is practical and effective, and the test result from the sensor is in good agreement with the theoretical value. The experiments in the library show the validity of the calibration method and the excellent performance of the sensor.
引用
收藏
页码:2842 / 2845
页数:4
相关论文
共 15 条
  • [1] HVDC connection of offshore wind farms to the transmission system
    Bresesti, Paola
    Kling, Wil L.
    Hendriks, Ralph L.
    Vailati, Riccardo
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2007, 22 (01) : 37 - 43
  • [2] Kasaba Y, 2005, AGU FALL M
  • [3] Analysis of Electric Field, Ion Flow Density, and Corona Loss of Same-Tower Double-Circuit HVDC Lines Using Improved FEM
    Liu, Jie
    Zou, Jun
    Tian, Jihuan
    Yuan, Jiansheng
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (01) : 482 - 483
  • [4] A MEMS-Based Electric Field Sensor for Measurement of High-Voltage DC Synthetic Fields in Air
    Ma, Qing
    Huang, Kaitian
    Yu, Zhanqing
    Wang, Zheyao
    [J]. IEEE SENSORS JOURNAL, 2017, 17 (23) : 7866 - 7876
  • [5] DEVELOPMENT OF FIELD-MILL INSTRUMENTS FOR GROUND-LEVEL AND ABOVE-GROUND ELECTRIC-FIELD MEASUREMENT UNDER HVDC TRANSMISSION-LINES
    MARUVADA, PS
    DALLAIRE, RD
    PEDNEAULT, R
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1983, 102 (03): : 738 - 744
  • [6] GENERATION AND MEASUREMENT OF DC ELECTRIC-FIELDS WITH SPACE-CHARGE
    MISAKIAN, M
    [J]. JOURNAL OF APPLIED PHYSICS, 1981, 52 (05) : 3135 - 3144
  • [7] Qin B., 1986, HIGH VOLT ENG, V1, P61
  • [8] Ren JL, 2017, INT J INF SYST SERV, V9, P1, DOI 10.4018/IJISSS.2017040101
  • [9] Electrostatic charge and field sensors based on micromechanical resonators
    Riehl, PS
    Scott, KL
    Muller, RS
    Howe, RT
    Yasaitis, JA
    [J]. JOURNAL OF MICROELECTROMECHANICAL SYSTEMS, 2003, 12 (05) : 577 - 589
  • [10] Tihanyi L, 1995, ELECTROMAGN COMPAT P, V1, P56