Parametric analysis of ejector working characteristics in the refrigeration system

被引:76
作者
Chen, Jianyong [1 ]
Havtun, Hans [1 ]
Palm, Bjorn [1 ]
机构
[1] Royal Inst Technol KTH, Dept Energy Technol, Div Appl Thermodynam & Refrigerat, SE-10044 Stockholm, Sweden
关键词
Ejector refrigeration; COP; Entrainment ratio; Irreversibility; Efficiency; EXERGY ANALYSIS; WATER;
D O I
10.1016/j.applthermaleng.2014.04.047
中图分类号
O414.1 [热力学];
学科分类号
摘要
A detailed investigation of ejector working characteristics in terms of refrigeration efficiency, ejector entrainment ratio, and irreversibilities in each ejector component (nozzle, mixing chamber and diffuser) is carried out by using R141b, R245fa and R600a as the working fluids. The aim of this paper is to generalize the interactions and relationships of various ejector parameters to get better understanding of the ejector working characteristics in the refrigeration system. External and internal ejector parameters are studied separately. The operating conditions and ejector component efficiencies have significant influence on the ejector behavior, and different refrigerants perform distinctively different in the ejector refrigeration system. However, effects of superheat of the three working fluids are negligible. The irreversibility related to the shock process dominates in the diffuser and plays an important role in the ejector performance. Further attention is paid on an analysis of quantifying the ejector component efficiencies based on published test data. Correlations are established to estimate the ejector efficiency and to show how ejector parameters interact. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:130 / 142
页数:13
相关论文
共 22 条
[1]   OTHER OPTIONS OF MASS AND ENERGY INPUT FOR STEAM JET REFRIGERATION SYSTEMS [J].
ABDELAAL, HK ;
ALZAKRI, AS ;
ELSARHA, ME ;
ELSWIFY, ME ;
ASSASSA, GM .
CHEMICAL ENGINEERING JOURNAL AND THE BIOCHEMICAL ENGINEERING JOURNAL, 1990, 45 (02) :99-110
[2]   Exergy analysis of ejector-refrigeration cycle using water as working fluid [J].
Alexis, GK .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2005, 29 (02) :95-105
[3]   Thermodynamic optimization of ejector actuated refrigerating cycles [J].
Angelino, Gianfranco ;
Invernizzi, Costante .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (03) :453-463
[4]   Ejector irreversibility characteristics [J].
Arbel, A ;
Shklyar, A ;
Hershgal, D ;
Barak, M ;
Sokolov, M .
JOURNAL OF FLUIDS ENGINEERING-TRANSACTIONS OF THE ASME, 2003, 125 (01) :121-129
[5]  
Arora ChandraPrakash., 2000, REFRIG AIR CONDITION
[6]   MECHANICAL REFRIGERATION USING AN EJECTOR INJECTOR TO TRANSFER THE WORKING FLUID FROM THE EVAPORATOR TO THE CONDENSER [J].
BEVILACQUA, P .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1991, 14 (03) :137-139
[7]   Investigation of ejectors in refrigeration system: Optimum performance evaluation and ejector area ratios perspectives [J].
Chen, Jianyong ;
Havtun, Hans ;
Palm, Bjorn .
APPLIED THERMAL ENGINEERING, 2014, 64 (1-2) :182-191
[8]   Recent developments in ejector refrigeration technologies [J].
Chen, Xiangjie ;
Omer, Siddig ;
Worall, Mark ;
Riffat, Saffa .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2013, 19 :629-651
[9]   A 1-D analysis of ejector performance [J].
Huang, BJ ;
Chang, JM ;
Wang, CP ;
Petrenko, VA .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1999, 22 (05) :354-364
[10]  
KEENAN JH, 1950, J APPL MECH-T ASME, V17, P299