Performance of a lab-scale membrane-based energy exchanger

被引:16
作者
Alonso, Maria Justo [1 ]
Mathisen, Hans Martin [2 ]
Aarnes, Sofie [3 ]
Liu, Peng [2 ]
机构
[1] SINTEF Bldg & Infrastruct, Alfred Getz Vei 3, N-7465 Trondheim, Norway
[2] NTNU, Kolbjorn Hejesv 1D, N-7465 Trondheim, Norway
[3] Univ Oslo, N-0316 Oslo, Norway
关键词
Sensible heat; Latent heat; Cold climate; Thermal comfort; Energy recovery; FROST FORMATION; RECOVERY; HEAT;
D O I
10.1016/j.applthermaleng.2015.11.119
中图分类号
O414.1 [热力学];
学科分类号
摘要
Efficient energy recovery from used air with the goal of reducing energy use is important for realizing low energy houses. Rotary heat exchangers are very energy efficient, but have the drawback of transferring odours from exhaust air to fresh supply air. To avoid this, flat plate heat exchangers are commonly used where odour transfer might cause problems. Nevertheless, these may not properly handle water condensation and frost formation at low outdoor temperatures. The so-called membrane-based energy exchangers are an alternative to the flat plate heat exchanger. In a membrane-based exchanger, moisture is transferred from. the humid exhaust air to the dry supply air, avoiding condensation at the exhaust airside. In this work, a membrane energy exchanger was compared to a thin non-vapour permeable plastic foil heat exchanger. The study focused on verifying condensation and freezing problems and evaluating the performance of the membrane energy exchanger. The experiments showed that non-permeable heat exchangers have problems with condensation and freezing under test conditions. Under the same conditions, the membrane-based exchanger did not experience the same problems. However, additional problems with swelling of the membrane in high humidity conditions showed that the tested membrane type had drawbacks and needs further development to become commercially applicable. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1244 / 1254
页数:11
相关论文
共 22 条
[1]  
Aarnes S. M., 2012, THESIS
[2]   A new approach to regenerating heat and moisture in ventilation systems [J].
Adstov, Yu. I. ;
Mezentsev, I. V. ;
Mukhin, V. A. .
ENERGY AND BUILDINGS, 2008, 40 (03) :204-208
[3]  
Alonso M. Justo, 2013, INVESTIGATION PROTOT
[4]  
Alonso M. Justo, 2012, 7 COLD CLIM C NOV 12
[5]   Review of heat/energy recovery exchangers for use in ZEBs in cold climate countries [J].
Alonso, Maria Justo ;
Liu, Peng ;
Mathisen, Hans M. ;
Ge, Gaoming ;
Simonson, Carey .
BUILDING AND ENVIRONMENT, 2015, 84 :228-237
[6]   Frost formation in the cross-flow plate heat exchanger for energy recovery [J].
Anisimov, Sergey ;
Jedlikowski, Andrzej ;
Pandelidis, Demis .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2015, 90 :201-217
[7]  
[Anonymous], 1997, HDB FUND
[8]  
[Anonymous], 2008, BUILD EN DAT BOOK, P2009
[9]   Frost formation in rotary heat and moisture exchangers [J].
Bilodeau, S ;
Brousseau, P ;
Lacroix, M ;
Mercadier, Y .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1999, 42 (14) :2605-2619
[10]  
Coleman W.H., 1999, EXPT UNCERTAINTY ANA