Evaluation of Electric-Thermal Performance of High-Power Contact Systems With the Voltage-Temperature Relation

被引:20
作者
Gatzsche, Michael [1 ]
Luecke, Nils [1 ]
Grossmann, Steffen [1 ]
Kufner, Tom [2 ]
Freudiger, George [2 ]
机构
[1] Tech Univ Dresden, Inst Elect Power Syst & High Voltage Engn, D-01062 Dresden, Germany
[2] Multicontact AG, CH-4123 Allschwil, Switzerland
来源
IEEE TRANSACTIONS ON COMPONENTS PACKAGING AND MANUFACTURING TECHNOLOGY | 2017年 / 7卷 / 03期
关键词
Contact resistance; power contacts; short-circuit currents; steady-state temperature rise; transient temperature rise; voltage-temperature relation; APPLICABILITY; CONDUCTION;
D O I
10.1109/TCPMT.2016.2587360
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Researchers and engineers use the voltage-temperature (V-T) relation to calculate the maximum temperature of electric contacts from contact voltage drop and thus evaluate their performance. However, researchers found deviations from the V-T relation for large contact systems when heat dissipation to the environment becomes significant. We investigated the applicability of the V-T relation to high-power contact systems with spring-loaded contact elements. Such connections with rated normal currents of several kiloamperes and short-time withstand currents of several tens of kiloamperes are used in high-voltage switchgear. We loaded a connector cooled by a potent variable water cooling system with continuous ac up to 6.7 kA to create a multitude of thermally symmetric and asymmetric steady-state operating points. However, temperature differences in the contact system remained below 20 K. Temperature differences calculated with the V-T relation were 23% higher than the measured values, but nevertheless deliver an assessment of the maximum contact system temperature valid for engineering purposes. In the case of a 1-s, 20-kA short-circuit current, a transient temperature rise occurs in the contact system. We numerically calculated the development of the spatial temperature distribution over time and found significant differences to the electric-thermal steady state. While contacts react very quickly and even oscillate with twice the line frequency on ac load, the contact element and conductor continuously heat up and do not reach the steady state.
引用
收藏
页码:317 / 328
页数:12
相关论文
共 29 条
[1]   A Multiphysics Finite Element Model of a 35A Automotive Connector Including Multiscale Rough Surface Contact [J].
Angadi, Santosh V. ;
Jackson, Robert L. ;
Choe, Song-yul ;
Flowers, George T. ;
Lee, Bong-Yi ;
Zhong, Liang .
JOURNAL OF ELECTRONIC PACKAGING, 2012, 134 (01)
[2]  
[Anonymous], P IEEE 60 HOLM C EL
[3]  
[Anonymous], 2015, THERM
[4]  
[Anonymous], 2013, ANS 15 0 HELP
[5]  
[Anonymous], 2005, WERKST CU ETP
[6]  
[Anonymous], 2011, 60865 IEC
[7]   Thermo-mechanical study of a power connector [J].
Carvou, E. ;
El Abdi, R. ;
Razafiarivelo, J. ;
Benjemaa, N. ;
Zindine, E. M. .
MEASUREMENT, 2012, 45 (05) :889-896
[8]  
Gatzsche M., 2015, CRC HDB CHEM PHYS, P72
[9]  
Gatzsche M, 2015, ELECTR CONTACT, P29, DOI 10.1109/HOLM.2015.7354951
[10]   ELECTRICAL CONDUCTION IN SOLIDS .2. THEORY OF TEMPERATURE-DEPENDENT CONDUCTORS [J].
GREENWOOD, JA ;
WILLIAMSON, JBP .