Thermodynamic analysis of a FBCC steam power plant

被引:22
作者
Eskin, Nurdil [2 ]
Gungor, Afsin [1 ]
Ozdemir, Koray [2 ]
机构
[1] Nigde Univ, Dept Mech Engn, Fac Engn & Architecture, TR-51100 Nigde, Turkey
[2] Istanbul Tech Univ, Fac Mech Engn, TR-34437 Istanbul, Turkey
关键词
Thermodynamic analysis; Exergy; Second law; Optimization; Power plant; Fluidized bed; FLUIDIZED-BED COMBUSTION; EXERGY ANALYSIS; COAL COMBUSTORS; EFFICIENCY;
D O I
10.1016/j.enconman.2009.05.035
中图分类号
O414.1 [热力学];
学科分类号
摘要
This article presents the analysis of first and second laws of thermodynamics in a 7.7 MW steam power plant located in Torbali (Izmir, Turkey). it involves a fluidized bed, a waste heat boiler (WHB) and an economizer as subsystems. Fans, pumps, cyclone and chimney are also considered through the analysis as auxiliary systems in the thermal plant. The analysis is performed for the whole system and subsystems by considering the available energy balance. In this analysis which consists of a detailed fluidized bed coal combustor (FBCC) model, the amount of irreversibilities occurring in the system is calculated at each location. Analysis results are compared with the test results obtained from the measurements at several locations in the system and good agreement is observed. These measured values are the temperatures at three levels in the FBCC and boiler, economizer exit temperatures as well as flue gas composition at the boiler exit and steam flow rate. The maximum error observed in temperature values and steam flow rate is about 3.03% and 4.03%, respectively. Through the developed and validated model, effects of excess air and ambient temperature on first and second law efficiency of the subsystems and overall system are investigated. The second-law analysis reveals that the FBCC has the largest irreversibility, with about 80.4% of the total system exergy loss. The FBCC temperature, first and second law efficiencies decrease 19.8%, 5.1% and 5.2%, respectively, as the excess air increases from 10% to 70%. Also steam flow rate decreases 5.1%. As the ambient temperature increases from 25 to 45 degrees C, the FBCC temperature, system first and second law efficiencies increase 0.8%, 1.3%, and 1.3%, respectively. (C) 2009 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2428 / 2438
页数:11
相关论文
共 31 条
[1]   Circulating fluidized bed combustion in the turbulent regime:: modelling of carbon combustion efficiency and sulphur retention [J].
Adanez, J ;
Gayán, P ;
Grasa, G ;
de Diego, LF ;
Armesto, L ;
Cabanillas, A .
FUEL, 2001, 80 (10) :1405-1414
[2]  
BASU P, 1999, BOILERS BURNERS
[3]  
Bejan A, 1995, Thermal design and optimization
[4]  
BORGWARDT RH, 1970, ENVIRON SCI TECHNOL, V4, P49
[5]   Application of the methodology to estimate the energy-ecologic efficiency of fluidized bed boilers [J].
Cârdu, M ;
Baica, M .
ENERGY CONVERSION AND MANAGEMENT, 2001, 42 (07) :867-876
[6]   The role of exergy in energy policy making [J].
Dincer, I .
ENERGY POLICY, 2002, 30 (02) :137-149
[7]  
ESKIN N, 1995, B ISTANBUL TU, V48, P11
[8]  
Gungor A, 2005, INT J THERMODYN, V8, P127
[9]   Analysis of combustion efficiency in CFB coal combustors [J].
Gungor, Afsin .
FUEL, 2008, 87 (07) :1083-1095
[10]  
Incropera F.P., 1998, FUNDAMENTALS HEAT MA, V4th