Different Bonding Types of Scilla-Villafranca (Sicily-Calabria) 43-km Double-Circuit AC 380-kV Submarine-Land Cables

被引:18
作者
Benato, Roberto [1 ]
Sessa, Sebastian Dambone [1 ]
De Zan, Riccardo [2 ]
Guarniere, Maria Rosaria [2 ]
Lavecchia, Giuseppe [2 ]
Labini, Paolo Sylos [2 ]
机构
[1] Univ Padua, Dept Ind Engn, I-35131 Padua, Italy
[2] Terna Rete Italia SpA, I-00156 Rome, Italy
关键词
Cross-bonding; multiconductor cell analysis (MCA); sequence impedances; solid-bonding; submarine cables; OVERHEAD;
D O I
10.1109/TIA.2015.2448676
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This paper describes and analyzes the extra-high-voltage double-circuit cable line between Sicily and Calabria which is a reinforcement of the Italian southern transmission grid. This is one of the longest ac submarine links in the world. The multiconductor cell analysis of this land-submarine double-circuit single-core cables has been compared with an electromagnetic transient program model with a very good agreement. The different choices of bonding systems implemented in the real Italian installation are theoretically justified by means of the two-software comparison.
引用
收藏
页码:5050 / 5057
页数:8
相关论文
共 9 条
[1]  
[Anonymous], 2014, IEC 60287-1-1
[2]  
[Anonymous], 6028712 IEC
[3]  
Benato R., 2012, P IEEE PES T D C EXP, P1
[4]   Operating capability of ac EHV mixed lines with overhead and cables links [J].
Benato, Roberto ;
Paolucci, Antonio .
ELECTRIC POWER SYSTEMS RESEARCH, 2008, 78 (04) :584-594
[5]   Zero sequence behaviour of a double-circuit overhead line [J].
Benato, Roberto ;
Sessa, Sebastian Dambone ;
Guglielmi, Fabio ;
Partal, Ertugrul ;
Tleis, Nasser .
ELECTRIC POWER SYSTEMS RESEARCH, 2014, 116 :419-426
[7]  
Colla L., 2008, C4116 CIGR
[8]  
Rebolini M., 2008, ENERG ELETTR, V4, P15
[9]  
Rebuffat L., 1984, INSTALLATION SUBMARI