Influence of reduced VAV flow settings on indoor thermal comfort in an office space

被引:18
作者
Gangisetti, Kavita [1 ]
Claridge, David E. [1 ]
Srebric, Jelena [2 ]
Paulus, Mitchell T. [1 ]
机构
[1] Texas A&M Univ, College Stn, TX 77845 USA
[2] Univ Maryland, College Pk, MD 20742 USA
关键词
CFD; thermal comfort; draught; diffusers; turbulence; NUMERICAL-MODELS; AIR MOVEMENT; BUILDINGS; ROOM; OPENINGS; DRAFT;
D O I
10.1007/s12273-015-0254-3
中图分类号
O414.1 [热力学];
学科分类号
摘要
The air temperature distribution in a space with reduced diffuser flow rates and heat loads was studied using simulation. Computational fluid dynamics (CFD) was used to analyze the room air distribution from a side wall diffuser at the design flow rate, and the results were validated with experimental data. CFD was used to predict occupant discomfort under a range of reduced diffuser flow rates. It was found for diffuser flow rates above 30% of the design flow rate that the temperature influence from the jet was minimal. At these flow rates, there was nearly a uniform temperature distribution in the occupied zone. The predicted maximum value of percentage of dissatisfied occupants within the space began to increase for diffuser flow rates below 30% of the design flow rate. The percent dissatisfaction at 1 m room height was greater than 25% for the lowest diffuser flow rate tested (15% of the design flow rate) directly under the diffuser, which was the highest of the test cases, but was 5% or less throughout more than 90% of the room. In contrast, at the higher flow rates, the percent dissatisfied index was 5% or less in only 60%-80% of the room due to increased velocity. Evidence of dumping was already found at the traditional minimum flow rate setting of 30% of design, and so there would be little harm in reducing the minimum flow rate further. Reducing the flow rate below 30% of design just moved the location of the dumping closer to the diffuser. For very low diffuser flow rates (below 30% of the design flow rate), it is recommended that desks be placed away from the supply diffuser to avoid discomfort. Overall, the simulation results indicate that uniform temperatures are maintained in the room at flow rates as low as 15% of design except immediately under the diffuser. This suggests that the VAV minimum flow rates can be set below 30% of design flow as long as the diffuser is at least 1 m from an occupant's position.
引用
收藏
页码:101 / 111
页数:11
相关论文
共 42 条
[1]  
[Anonymous], 2013, 552013 ASHRAE ANSIAS
[2]  
[Anonymous], RP1515 ASHRAE
[3]  
Ansys, 2013, ANSYS MECH US GUID
[4]   A study of occupant cooling by personally controlled air movement [J].
Arens, E ;
Xu, TF ;
Miura, K ;
Hui, Z ;
Fountain, M ;
Bauman, F .
ENERGY AND BUILDINGS, 1998, 27 (01) :45-59
[5]   Air movement acceptability limits and thermal comfort in Brazil's hot humid climate zone [J].
Candido, C. ;
de Dear, R. J. ;
Lamberts, R. ;
Bittencourt, L. .
BUILDING AND ENVIRONMENT, 2010, 45 (01) :222-229
[6]   A review of indices for the long-term evaluation of the general thermal comfort conditions in buildings [J].
Carlucci, Salvatore ;
Pagliano, Lorenzo .
ENERGY AND BUILDINGS, 2012, 53 :194-205
[7]  
CHARLES KE, 2003, RR162 IRC NAT RES CO
[8]   COMPARISON OF DIFFERENT K-EPSILON MODELS FOR INDOOR AIR-FLOW COMPUTATIONS [J].
CHEN, Q .
NUMERICAL HEAT TRANSFER PART B-FUNDAMENTALS, 1995, 28 (03) :353-369
[9]  
Chen Q, 1991, P 12 AIVC C OTT CAN, P1
[10]   Thermal comfort models: A review and numerical investigation [J].
Cheng, Yuanda ;
Niu, Jianlei ;
Gao, Naiping .
BUILDING AND ENVIRONMENT, 2012, 47 :13-22