Effect of Static Power Supply in Alternator Used for Short-Circuit Testing-Observation of Shaft Voltage

被引:13
作者
Datta, Arun Kumar [1 ]
Dubey, Manisha [2 ]
Jain, Shailendra [2 ]
机构
[1] Cent Power Res Inst, Bhopal 462023, MP, India
[2] Maulana Azad Natl Inst Technol, Dept Elect Engn, Bhopal 462023, MP, India
关键词
AC motor drives; electrostatic discharges; frequency conversion; synchronous machines; thyristor converter; INDUCTION-MOTOR DRIVE; BEARING CURRENTS; INVERTER SCHEME; ELIMINATION; REDUCTION; PWM; SYSTEMS;
D O I
10.1109/TPEL.2014.2300185
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
All electrical power equipment, before putting into service, have to pass through numbers of tests to prove their functional performance. In this context, short-circuit test is one of the vital performance tests. A high power alternator used in short-circuit test laboratory is taken as a study object in this paper. Normally, a motor is used as the prime mover for this type of alternator. In this system, the driving motor is eliminated and a thyristor-based static drive is placed to run the machine. The benefit with the static drive is that the single machine can be operated in dual mode, either as a motor or as an alternator. But the negative side of this system is the generation of voltages in the machine shaft. Machine bearings are susceptible to failure if these unwanted shaft voltages cause a high level of bearing currents and persist for a prolonged period. Very little studies were carried out on the power generators related to shaft voltages with perspective to static power supply. This paper explains the details of the static drives applied on this machine for different operational modes. Various causes of generation of shaft voltages are analyzed in view of this special alternator. The outcome of this paper can also be applicable to other large synchronous machines.
引用
收藏
页码:6074 / 6080
页数:7
相关论文
共 25 条
[1]  
Adabi Jafar, 2007, P AUSTR U POW ENG C, P641
[2]  
Akagi H, 2004, IEEE T IND APPL, V40, P1162, DOI [10.1109/TIA.2004.830748, 10.1109/tia.2004.830748]
[3]   A Hybrid Active Filter for a Three-Phase 12-Pulse Diode Rectifier Used as the Front End of a Medium-Voltage Motor Drive [J].
Akagi, Hirofumi ;
Isozaki, Kohei .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2012, 27 (01) :69-77
[4]   SHAFT VOLTAGES IN GENERATORS WITH STATIC EXCITATION SYSTEMS - PROBLEMS AND SOLUTION [J].
AMMANN, C ;
REICHERT, K ;
JOHO, R ;
POSEDEL, Z .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 1988, 3 (02) :409-419
[5]   Dual two-level inverter scheme with common mode voltage elimination for an induction motor drive [J].
Baiju, MR ;
Mohapatra, KK ;
Kanchan, RS ;
Gopakumar, K .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2004, 19 (03) :794-805
[6]   Experience with variable-frequency drives and motor bearing reliability [J].
Bell, S ;
Cookson, TJ ;
Cope, SA ;
Epperly, RA ;
Fischer, A ;
Schlegel, DW ;
Skibinski, GL .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2001, 37 (05) :1438-1446
[7]  
CHEN S, 1998, IEEE IND APPL MAG, V4, P32
[8]  
Datta A. K., 2012, P IEEE STUD C EL EL, P1
[9]  
Datta A. K., 2012, INT J ELECT COMMUN T, V3, P472
[10]   Effect of PWM inverters on AC motor bearing currents and shaft voltages [J].
Erdman, JM ;
Kerkman, RJ ;
Schlegel, DW ;
Skibinski, GL .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1996, 32 (02) :250-259