Numerical investigation on the thermal-flow performance of humid air-water in the interspace outside staggered tube bundles

被引:17
作者
Ma, Hongqiang [1 ,2 ,3 ]
Liu, Yemin [1 ,2 ]
Hou, Caiqin [2 ]
Wang, Gang [2 ]
Luo, Xinmei [1 ]
机构
[1] East China Jiaotong Univ, Sch Civil Engn & Architecture, Nanchang, Jiangxi, Peoples R China
[2] Lanzhou Univ Technol, Sch Civil Engn, Lanzhou, Peoples R China
[3] Sinopec Petr Engn Zhongyuan Corp, Puyang, Peoples R China
基金
中国国家自然科学基金;
关键词
Evaporative cooling; Heat and mass transfer; Pressure drop; CFD; Tube bundles; HEAT-TRANSFER; FALLING FILM; EVAPORATIVE CONDENSERS; WET; PLAIN; THICKNESS; BEHAVIOR; DESIGN; MODES; BARE;
D O I
10.1016/j.ijheatmasstransfer.2020.120784
中图分类号
O414.1 [热力学];
学科分类号
摘要
A new model was established to investigate the thermal-flow performance of humid air-water in the interspace outside staggered tube bundles. The formation of spray water film, heat and mass transfer process between humid air and spray water including spray water droplets and film were considered in this model. The influence of structure parameters was analyzed for thermal-flow performance of humid air-water in the interspace outside staggered tube bundles. It can be found that to increase the longitudinal and transverse distance between tube bundles can improve the heat transfer performance between spray water and wall of tube bundles, and decrease the pressure drop of humid air-water. But the mass transfer between spray water and humid air will only decrease with the transverse distance between tube bundles. Meanwhile, the relative humidity of humid air is not fully utilized at the top of staggered tube bundles when the transverse distance is more than 20 mm. Otherwise, the spray water will be lost heavily at the 19-24th rows of staggered tube bundles. The row number of staggered tube bundles should be reasonably designed in term of the transverse distance. The new correlations of heat transfer and pressure drop are also obtained in term of the simulation results. The Parker's correlation will be also recommended to design the mass transfer performance of that. (C) 2020 Elsevier Ltd. All rights reserved.
引用
收藏
页数:20
相关论文
共 21 条
  • [21] Numerical Investigation of the Air-Side Thermal Hydraulic Performance of a Louvered-Fin and Flat-Tube Heat Exchanger at Low Reynolds Numbers
    Erbay, L. Berrin
    Ugurlubilek, Nihal
    Altun, Ozge
    Dogan, Bahadir
    HEAT TRANSFER ENGINEERING, 2017, 38 (06) : 627 - 640