An experimental study on the heat transfer and pressure drop characteristics of electronics cooling heat sinks with FC-72 flow boiling

被引:16
作者
Kim, Chang-Hoon [1 ]
Lee, Min-Ju [1 ]
Park, Chang Yong [1 ]
机构
[1] Seoul Natl Univ Sci & Technol, Dept Mech Syst Design Engn, Seoul 01811, South Korea
关键词
Electronics cooling; FC-72; Flow boiling; Heat sink; Heat transfer; Pressure drop; JET IMPINGEMENT; 2-PHASE FLOW; GENERAL CORRELATION; REFRIGERATION SYSTEM; THERMAL MANAGEMENT; POROUS SURFACES; FINNED SURFACES; LIQUID; CHANNELS; FLUX;
D O I
10.1007/s12206-018-0249-y
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
An experimental study was performed to measure FC-72(C6F14) flow boiling heat transfer and pressure drop in heat sinks for electronics cooling. The heat sink had cooling cross section area of 38.0 x 37.0 mm with rectangular fins. The height, length and thickness of a fin was 5.0, 24.0 and 1.0 mm, respectively. The width of fluid channels between the fins was 1.0 mm. The heat sink consisted of a heating and cooling section, and a cover. Two types of heat sinks were used in this study. The two heat sinks were different only in the cover, and the machined depth of the cover was 5.0 and 8.0 mm, respectively. Electric heating from 100 to 300 W was supplied by cartridge heaters and it was equivalent to the heat flux from 71.12 to 213.4 kW/m(2) based on the cross section area of the cooled surface. The saturation temperatures of the FC-72 were from 59.8 degrees C to 71.5 degrees C during the experiment and the mass fluxes were from 24.2 to 230.0 kg/m(2)s. The trend of heat transfer and pressure drop variation with the change of vapor quality was similar to that of flow boiling in tubes such as the increase of heat transfer and pressure drop with the increase of vapor quality before dryout. Similar heat transfer coefficients and pressure drop values were measured under the same mass flow conditions for both types of heat sinks. In this study, the cooling performance with liquid water was also measured at the same heat sinks. The comparison of experimental data presented that the cooling capacity with FC-72 flow boiling was up to 330 % higher than that with liquid water. However, the FC-72 pressure drop was also significantly higher than water.
引用
收藏
页码:1449 / 1462
页数:14
相关论文
共 91 条
[31]  
Imran M., 2016, INT J AIRCOND REFRIG, V24
[32]  
Incropera F.P., 2013, Principles of Heat and Mass Transfer, V7th ed.
[33]  
*INEMI, 2004, EL MAN IN TECHN ROAD
[34]   Water cooled minichannel heat sinks for microprocessor cooling: Effect of fin spacing [J].
Jajja, Saad Ayub ;
Ali, Wajahat ;
Ali, Hafiz Muhammad ;
Ali, Aysha Maryam .
APPLIED THERMAL ENGINEERING, 2014, 64 (1-2) :76-82
[36]   Effect of sub-cooling on performance of a multi-jet two phase cooler with multi-scale porous surfaces [J].
Joshi, Shailesh N. ;
Dede, Ercan M. .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2015, 87 :110-120
[37]   Flow boiling heat transfer of R134a in the multiport minichannel heat exchangers [J].
Kaew-On, Jatuporn ;
Sakamatapan, Kittipong ;
Wongwises, Somchai .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2011, 35 (02) :364-374
[38]   Correlations for the prediction of boiling heat transfer in small-diameter channels [J].
Kew, PA ;
Cornwell, K .
APPLIED THERMAL ENGINEERING, 1997, 17 (8-10) :705-715
[39]   Evaluation of Various Channel Shapes of a Microchannel Heat Sink [J].
Khan, Aatif Ali ;
Kim, Kwang-Yong .
INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2016, 24 (03)
[40]  
Klein S.A., 2013, Engineering Equation Solver for Microsoft Windows Operating Systems, Commercial and Professional Versions