Automatic generation control of an interconnected two-area hybrid thermal system considering dish-stirling solar thermal and wind turbine system

被引:114
作者
Rahman, Asadur [1 ]
Saikia, Lalit Chandra [2 ]
Sinha, Nidul [2 ]
机构
[1] Natl Inst Technol Nagaland, Dept Elect & Elect Engn, Dimapur, Nagaland, India
[2] Natl Inst Technol Silchar, Dept Elect Engn, Silchar, Assam, India
关键词
Automatic generation control (AGC); Biogeography based optimization (BBO); Dish-stirling solar thermal system (DSTS); Hybrid system; Random load perturbation (RLP); Wind turbine system (WTS); SIGNAL STABILITY ANALYSIS; LOAD-FREQUENCY CONTROL; POWER-SYSTEM; DESIGN; PLANT; AGC;
D O I
10.1016/j.renene.2016.12.048
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This article presents automatic generation control (AGC) of an interconnected two-area hybrid thermal system with additional power generation from dish-Stirling solar thermal system (DSTS) and wind turbine system (WTS). Each area is equipped with Integral (I), Proportional-Integral (PI), and Proportional-Integral-Derivative (PID) as secondary controllers to regulate power output of thermal system and maintain the power balance. This facilitates maintaining the frequency close to its nominal value. Biogeography-based optimization (BBO) technique is used for simultaneous optimization of controller parameters. System dynamics are evaluated with step load perturbation and random load perturbation in Area1. The performance of PID is found improved in comparison to I and PI controller in terms of settling time, peak deviation and magnitude of oscillation. Investigation shows that BBO optimized PID controller parameters obtained at nominal conditions are robust enough and not necessary to optimize for wide changes in renewable energy sources, area capacity ratio, system loading, and inertia constant (H). Thus, integration of DSTS and WTS for AGC of interconnected system is safely attributed. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:41 / 54
页数:14
相关论文
共 32 条