Fast Disposal Method for Reducing Electricity Risk of Single-phase Ground Fault in Distribution Network

被引:0
作者
Qi, Mingjun [1 ]
Leng, Hua [1 ]
Zhang, Zhidan [1 ]
Yang, Lei [2 ]
Peng, Shasha [2 ]
Zeng, Xiangjun [2 ]
机构
[1] State Grid Hunan Elect Power Co, State Grid Hunan Elect Power Corp Res Inst, Changsha, Hunan, Peoples R China
[2] Changsha Univ Sci & Technol, Collaborat Innovat Ctr Clean Energy & Elect Power, Changsha, Hunan, Peoples R China
来源
PROCEEDINGS OF 2017 CHINA INTERNATIONAL ELECTRICAL AND ENERGY CONFERENCE (CIEEC 2017) | 2017年
基金
中国国家自然科学基金;
关键词
distribution network; electric shock risk; fault phase voltage; full compensation; single-phase ground fault;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In order to realize the active arc suppression of the single-phase ground fault of the non-effective grounding system and reduce electricity risk, a fast disposal method for reducing the risk of electric shock of single-phase ground fault was proposed. When a single-phase ground fault occurred, the fault point was first located by the traveling wave positioning technology, and the voltage drop between the fault point and the power bus was calculated. The fault phase voltage was suppressed to zero through injecting current to control zero sequence voltage, which achieved full compensation of fault current and realized the purpose of arc suppression. The simulation results showed that the method was not affected by fault resistance, can quickly suppress the fault phase voltage, realize the full compensation of the ground fault point current of the distribution system, and effectively improve the safety level of the personal and equipment.
引用
收藏
页码:554 / 558
页数:5
相关论文
共 15 条
  • [1] [Anonymous], P IEEE BIOCAS
  • [2] Petersen Coil Regulators Analysis Using a Real-Time Digital Simulator
    Brenna, Morris
    De Berardinis, Ettore
    Carpini, Luca Delli
    Paulon, Pietro
    Petroni, Paola
    Sapienza, Gianluca
    Scrosati, Giorgio
    Zaninelli, Dario
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (03) : 1479 - 1488
  • [3] Cao J., 2015, ELECT MEASUREMENT IN, P32
  • [4] A Model Predictive Control-Based Common-Mode Voltage Suppression Strategy for Voltage-Source Inverter
    Guo, Leilei
    Zhang, Xing
    Yang, Shuying
    Xie, Zhen
    Cao, Renxian
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2016, 63 (10) : 6115 - 6125
  • [5] Analysis of Temporary Overvoltages During Open-Phase Faults in Distribution Networks With Resonant Grounding
    Kalyuzhny, Aaron
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (01) : 420 - 427
  • [6] Li Xiaobo, 2011, Electric Power Automation Equipment, V31, P116
  • [7] [刘维功 Liu Weigong], 2014, [电网技术, Power System Technology], V38, P2008
  • [8] Qu Yi-long, 2007, Relay, V35, P29
  • [9] [王阳 Wang Yang], 2012, [电力系统自动化, Automation of Electric Power Systems], V36, P143
  • [10] Winter Klaus M., 2005, 18 INT C EL DISTR CI, P7