Simulation of dynamics and control of a double-effect LiBr-H2O absorption chiller

被引:59
作者
Shin, Younggy [1 ]
Seo, Jung Ah [1 ]
Cho, Hyun Wook [2 ]
Nam, Sang Chul [2 ]
Jeong, Jin Hee [2 ]
机构
[1] Sejong Univ, Dept Mech Engn, Seoul 143747, South Korea
[2] Res & Technol Headquarters LS Cable Ltd, R&D Ctr, Machinery Technol Grp, Anyang 431080, Gyunggi Do, South Korea
关键词
Lithium bromide; LiBr-H2O; Absorption; Chiller; Dynamic model; Double-effect; Crystallization; Dilution cycle; SYSTEMS; PERFORMANCE; MODEL;
D O I
10.1016/j.applthermaleng.2009.01.006
中图分类号
O414.1 [热力学];
学科分类号
摘要
A dynamic model has been developed to simulate dynamic operation of a real double-effect absorption chiller. Dynamic behavior of working fluids in main components was modeled in first-order nonlinear differential equations based on heat and mass balances. Mass transport mechanisms among the main components were modeled by valve throttling, V tube overflow and solution sub-cooling. The nonlinear dynamic equations coupled with the subroutines to calculate thermodynamic properties of working fluids were solved by a numerical method. The dynamic performance of the model was compared with the test data of a commercial medium chiller. The model showed a good agreement with the test data except for the first 83 min during which different flow rates of the weak solution caused some discrepancy. It was found that the chiller dynamics is governed by the inlet temperatures of the cooling water and the chilled water when the heat input to the chiller is relatively constant. For a step change of load at constant inlet temperatures of the cooling water and the chilled water, the response time of the chilled water exit temperature was about 15 min and it was due to the thermal capacities of the chiller. The dilution cycle was found to be an essential means for improvement of control performance as well as anti-crystallization. (c) 2009 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2718 / 2725
页数:8
相关论文
共 12 条
[1]   Implementation of an object-oriented dynamic modeling library for absorption refrigeration systems [J].
Fu, DG ;
Poncia, G ;
Lu, Z .
APPLIED THERMAL ENGINEERING, 2006, 26 (2-3) :217-225
[2]  
*ISA, 2002, ISA7501012002
[3]   Dynamic simulation of an absorption heat pump for recovering low grade waste heat [J].
Jeong, S ;
Kang, BH ;
Karng, SW .
APPLIED THERMAL ENGINEERING, 1998, 18 (1-2) :1-12
[4]   Thermodynamic properties of lithium bromide-water solutions at high temperatures [J].
Kaita, Y .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2001, 24 (05) :374-390
[5]   A dynamic simulation model for transient absorption chiller performance. Part II: Numerical results and experimental verification [J].
Kohlenbach, P. ;
Ziegler, F. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (02) :226-233
[6]   A dynamic simulation model for transient absorption chiller performance. Part I: The model [J].
Kohlenbach, P. ;
Ziegler, F. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (02) :217-225
[7]  
LEMMON EW, 2006, REFROP REFERENCE FLU
[8]   Absorption chiller crystallization control strategies for integrated cooling heating and power systems [J].
Liao, Xiaohong ;
Radermacher, Reinhard .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2007, 30 (05) :904-911
[9]   Use of neural networks and expert systems to control a gas/solid sorption chilling machine [J].
Palau, A ;
Velo, E ;
Puigjaner, L .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1999, 22 (01) :59-66
[10]   Solid-liquid phase equilibrium in the systems of LiBr-H2O and LiCl-H2O [J].
Patek, J. ;
Klomfar, J. .
FLUID PHASE EQUILIBRIA, 2006, 250 (1-2) :138-149