摘要
Widespread adoption of innovative water conservation strategies has potential unintended consequences for aesthetics and public health. A cross-section of green buildings were surveyed and compared to typical conventional buildings in terms of water retention time (i.e., water age), water chemistry, and levels of opportunistic pathogen genetic markers. Water age was estimated to be 2-6.7 months in an off-grid office, an average of 8 days in a Leadership in Environmental Engineering Design certified healthcare suite, and was increased to 2.7 days from 1 day due to installation of a solar "pre-heat" water tank in a net-zero energy house. Chlorine and chloramine residuals were often completely absent in the green building systems, decaying up to 144 times faster in premise plumbing with high water age when compared to distribution system water. Concentration of 16S rRNA and opportunistic pathogen genus level genetic markers were 1-4 orders of magnitude higher in green versus conventional buildings. This study raises concerns with respect to current green water system practices and the importance of considering potential public health impacts in the design of sustainable water systems.
引用
收藏
页码:164 / 173
页数:10
相关论文
共 62 条
  • [1] Real-time PCR detection of pathogenic microorganisms in roof-harvested rainwater in Southeast Queensland, Australia
    Ahmed, W.
    Huygens, F.
    Goonetilleke, A.
    Gardner, T.
    [J]. APPLIED AND ENVIRONMENTAL MICROBIOLOGY, 2008, 74 (17) : 5490 - 5496
  • [2] Health Risk from the Use of Roof-Harvested Rainwater in Southeast Queensland, Australia, as Potable or Nonpotable Water, Determined Using Quantitative Microbial Risk Assessment
    Ahmed, W.
    Vieritz, A.
    Goonetilleke, A.
    Gardner, T.
    [J]. APPLIED AND ENVIRONMENTAL MICROBIOLOGY, 2010, 76 (22) : 7382 - 7391
  • [3] Ahmed W, 2010, CAN J MICROBIOL, V56, P471, DOI [10.1139/W10-037, 10.1139/w10-037]
  • [4] RISK-FACTORS FOR CONTAMINATION OF DOMESTIC HOT WATER-SYSTEMS BY LEGIONELLAE
    ALARY, M
    JOLY, JR
    [J]. APPLIED AND ENVIRONMENTAL MICROBIOLOGY, 1991, 57 (08) : 2360 - 2367
  • [5] Microbiological investigations of rainwater and graywater collected for toilet flushing
    Albrechtsen, HJ
    [J]. WATER SCIENCE AND TECHNOLOGY, 2002, 46 (6-7) : 311 - 316
  • [6] [Anonymous], THESIS VIRGINIA TECH
  • [7] [Anonymous], BOMA BEST EN ENV REP
  • [8] [Anonymous], LEG CONTR GUID
  • [9] [Anonymous], P INT WAT ASS LEAD E
  • [10] [Anonymous], AV TEMP SHALL GROUND