The influence of lightning induced voltage on the distribution power line polymer insulators

被引:7
|
作者
Izadi, Mahdi [1 ,2 ]
Abd Rahman, Muhammad Syahmi [1 ]
Ab-Kadir, Mohd Zainal Abidin [1 ]
Gomes, Chandima [1 ]
Jasni, Jasronita [1 ]
Hajikhani, Maryam [1 ]
机构
[1] Univ Putra Malaysia, Fac Engn, Ctr Electromagnet & Lightning Protect Res CELP, Serdang, Malaysia
[2] Islamic Azad Univ, Dept Elect Engn, Firoozkooh Branch, Firoozkooh, Iran
来源
PLOS ONE | 2017年 / 12卷 / 02期
关键词
WIRES;
D O I
10.1371/journal.pone.0172118
中图分类号
O [数理科学和化学]; P [天文学、地球科学]; Q [生物科学]; N [自然科学总论];
学科分类号
07 ; 0710 ; 09 ;
摘要
Protection of medium voltage (MV) overhead lines against the indirect effects of lightning is an important issue in Malaysia and other tropical countries. Protection of these lines against the indirect effects of lightning is a major concern and can be improved by several ways. The choice of insulator to be used for instance, between the glass, ceramic or polymer, can help to improve the line performance from the perspective of increasing the breakdown strength. In this paper, the electrical performance of a 10 kV polymer insulator under different conditions for impulse, weather and insulator angle with respect to a cross-arm were studied (both experimental and modelling) and the results were discussed accordingly. Results show that the weather and insulator angle (with respect to the cross-arm) are surprisingly influenced the values of breakdown voltage and leakage current for both negative and positive impulses. Therefore, in order to select a proper protection system for MV lines against lightning induced voltage, consideration of the local information concerning the weather and also the insulator angles with respect to the cross-arm are very useful for line stability and performance.
引用
收藏
页数:22
相关论文
共 50 条
  • [41] Voltage waveforms induced in power lines by nearby lightning strikes
    Maslowski, Grzegorz
    Ziemba, Robert
    PRZEGLAD ELEKTROTECHNICZNY, 2022, 98 (10): : 161 - 164
  • [42] The Effects of Lightning Induced Overvoltages on Low Voltage Power Networks
    Costea, M.
    Nicoara, B.
    2009 IEEE BUCHAREST POWERTECH, VOLS 1-5, 2009, : 1890 - 1895
  • [43] Influence of Earthing Resistance on the Performance of Distribution Line Lightning Arrester
    Rahman, N. A. Abd.
    Abdullah, N.
    Ariffin, M. F.
    2010 ASIA-PACIFIC INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY & TECHNICAL EXHIBITION ON EMC RF/MICROWAVE MEASUREMENTS & INSTRUMENTATION, 2010, : 1538 - 1541
  • [44] The Influence of Low and Zero Resistance Insulators on the Voltage Distribution of Insulator Strings
    Yin Pengxiang
    Luo Hao
    Zheng Lei
    Hong Xiao
    Qu Kai
    Dong Zhen
    Fan Qiang
    Liu Guanghui
    Che Bin
    PROCEEDINGS OF THE 2018 13TH IEEE CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ICIEA 2018), 2018, : 2089 - 2094
  • [45] Research of Flashover of Power Line Insulators Due to High-Voltage Pulses With Power ON and Power OFF
    Parfenov, Y. V.
    Zdoukhov, L. N.
    Shurupov, A. V.
    Kozlov, A. V.
    IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2013, 55 (03) : 467 - 474
  • [46] Research on the influence factors of lightning-induced over-voltage on military power supply cables
    Xie, Pu
    Zhao, Jin-Cheng
    Wang, Chuan-Chuan
    Wang, Yong
    Binggong Xuebao/Acta Armamentarii, 2014, 35 (02): : 214 - 219
  • [47] Effect of Earth Conductivity and Length of Line on Lightning Induced Voltage of 10kV Overhead Distribution Lines
    Yu J.
    Fan Y.
    Wang J.
    Cai L.
    Zhou M.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2020, 40 (02): : 672 - 683
  • [48] Lightning Critical Flashover Voltage of High Voltage Insulators: Laboratory Measurements and Calculations
    Filipovic-Grcic, Dalibor
    Filipovic-Grcic, Bozidar
    Uglesic, Ivo
    INTERNATIONAL REVIEW OF ELECTRICAL ENGINEERING-IREE, 2012, 7 (02): : 4321 - 4328
  • [49] Estimation of the maximal voltage induced on an overhead line due to the nearby lightning
    Univ `Sv. Kiril i Metodij', Skopje, Mk
    IEEE Trans Power Delivery, 1 (315-324):
  • [50] Lightning-induced voltage on an overhead wire influenced by a branch line
    Michishita, K
    Ishii, M
    Hongo, Y
    IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (01) : 296 - 302