Heating, Ventilation, and Air Conditioning System Optimization Control Strategy Involving Fan Coil Unit Temperature Control

被引:18
作者
Lin, Chang-Ming [1 ]
Liu, Hsin-Yu [2 ]
Tseng, Ko-Ying [2 ]
Lin, Sheng-Fuu [1 ]
机构
[1] Natl Chiao Tung Univ, Inst Elect & Control Engn, 1001 Univ Rd, Hsinchu 30010, Taiwan
[2] Ind Technol Res Inst, Energy & Environm Res Labs, Rm 820,Bldg 51,8F,195,Sec 4,Chung Hsing Rd, Hsinchu 31040, Taiwan
来源
APPLIED SCIENCES-BASEL | 2019年 / 9卷 / 11期
关键词
HVAC energy conservation; optimal control; genetic algorithm; FCU group control; MODEL-PREDICTIVE CONTROL; THERMAL COMFORT; ENERGY OPTIMIZATION; CHILLER SYSTEM; BUILDINGS;
D O I
10.3390/app9112391
中图分类号
O6 [化学];
学科分类号
0703 ;
摘要
The objective of this study was to develop a heating, ventilation, and air conditioning (HVAC) system optimization control strategy involving fan coil unit (FCU) temperature control for energy conservation in chilled water systems to enhance the operating efficiency of HVAC systems. The proposed control strategy involves three techniques, which are described as follows. The first technique is an algorithm for dynamic FCU temperature setting, which enables the FCU temperature to be set in accordance with changes in the outdoor temperature to satisfy the indoor thermal comfort for occupants. The second technique is an approach for determining the indoor cold air demand, which collects the set FCU temperature and converts it to the refrigeration ton required for the chilled water system; this serves as the control target for ensuring optimal HVAC operation. The third technique is a genetic algorithm for calculating the minimum energy consumption for an HVAC system. The genetic algorithm determines the pump operating frequency associated with minimum energy consumption per refrigeration ton to control energy conservation. To demonstrate the effectiveness of the proposed HVAC system optimization control strategy combining FCU temperature control, this study conducted a field experiment. The results revealed that the proposed strategy enabled an HVAC system to achieve 39.71% energy conservation compared with an HVAC system operating at full load.
引用
收藏
页数:13
相关论文
共 24 条
[1]   Povl Ole Fanger's impact ten years later [J].
Alfano, Francesca Romana d'Ambrosio ;
Olesen, Bjarne Wilkens ;
Palella, Boris Igor .
ENERGY AND BUILDINGS, 2017, 152 :243-249
[2]  
ASHRAE, 2017, 552017 ASHRAE
[3]   Thermal adaptation in the built environment: a literature review [J].
Brager, GS ;
de Dear, RJ .
ENERGY AND BUILDINGS, 1998, 27 (01) :83-96
[4]   Transient simulation of vapour-compression packaged liquid chillers [J].
Browne, MW ;
Bansal, PK .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2002, 25 (05) :597-610
[5]   Thermal comfort control using a non-linear MPC strategy: A real case of study in a bioclimatic building [J].
Castilla, M. ;
Alvarez, J. D. ;
Normey-Rico, J. E. ;
Rodriguez, F. .
JOURNAL OF PROCESS CONTROL, 2014, 24 (06) :703-713
[6]   Occupant feedback based model predictive control for thermal comfort and energy optimization: A chamber experimental evaluation [J].
Chen, Xiao ;
Wang, Qian ;
Srebric, Jelena .
APPLIED ENERGY, 2016, 164 :341-351
[7]   Model predictive control for indoor thermal comfort and energy optimization using occupant feedback [J].
Chen, Xiao ;
Wang, Qian ;
Srebric, Jelena .
ENERGY AND BUILDINGS, 2015, 102 :357-369
[8]   Global optimization of absorption chiller system by genetic algorithm and neural network [J].
Chow, TT ;
Zhang, GQ ;
Lin, Z ;
Song, CL .
ENERGY AND BUILDINGS, 2002, 34 (01) :103-109
[9]  
Daghigh R, 2012, ADV MECH ENG APPL AM, V3, P278
[10]   Progress in thermal comfort research over the last twenty years [J].
de Dear, R. J. ;
Akimoto, T. ;
Arens, E. A. ;
Brager, G. ;
Candido, C. ;
Cheong, K. W. D. ;
Li, B. ;
Nishihara, N. ;
Sekhar, S. C. ;
Tanabe, S. ;
Toftum, J. ;
Zhang, H. ;
Zhu, Y. .
INDOOR AIR, 2013, 23 (06) :442-461