Transient Lightning Impulse Performance Analysis for Composite Transmission Line Tower

被引:12
作者
Huangfu, Youpeng [1 ]
Wang, Shuhong [1 ]
Tao, Xi [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Elect Engn, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
关键词
Composite transmission line tower; extended grounding structure; impulse performance; lightning strokes; SURGE RESPONSE; SOIL; MODEL;
D O I
10.1109/TEMC.2015.2410834
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, the transient impulse performances of a 330-kV composite transmission line tower under direct lightning strokes are comprehensively presented. An equivalent distributed parameter model combined with lumped capacitance elements for the tower is established. The wave impedances of the hybrid model are determined by using analytic equations. The lumped capacitances are calculated by 3-D finite element method (FEM). An accurate model for extended grounding structure (EGS) of the tower base considering the soil ionization is used to simulate its impulse performances. The wave process of the tower is analyzed by using the electromagnetic transient program (EMTP). The proper grounding conductor system is determined for the case of a superior lightning impulse performance considering three diverse grounding configurations. The influence of radius of the grounding conductor is assessed. The numerical electromagnetic field analysis, finite-difference time-domain (FDTD) simulation is applied to verify the validity of the presented hybrid model. Then, the influence of the wave-front time of the lightning current, the soil resistivity, the dimension of the EGS, and their combined effect on the transient impulse performances for the EGS are analyzed and discussed.
引用
收藏
页码:1103 / 1111
页数:9
相关论文
共 28 条
[1]  
ANSYS, 2013, ANSYS MAXWELL 16 0 S
[2]   Numerical electromagnetic field analysis on lightning surge response of tower with shield wire [J].
Baba, Y ;
Ishii, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (03) :1010-1015
[3]  
Bewley L.V., 1963, Traveling Waves on Transmission Systems
[4]  
CIGRE, 1991, 3301 CIGRE WG, V63
[5]   An algorithm for the exact evaluation of the underground lightning electromagnetic fields [J].
Delfino, Federico ;
Procopio, Renato ;
Rossi, Mansueto ;
Rachidi, Farhad ;
Nucci, Carlo Alberto .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2007, 49 (02) :401-411
[6]  
DOMMEL HW, 1969, IEEE T POWER AP SYST, VPA88, P388, DOI 10.1109/TPAS.1969.292459
[7]  
Elkins M, 2011, P IEEE PES 12 INT C, V5, P1
[8]  
Gorin B., 1984, Elecktrichestvo, V8, P64
[9]   Nonuniform transmission tower model for lightning transient studies [J].
Gutiérrez, JAR ;
Moreno, P ;
Naredo, JL ;
Bermúdez, JL ;
Paolone, A ;
Nucci, CA ;
Rachidi, F .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (02) :490-496
[10]  
Han-ming Li, 2010, 2010 International Conference on High Voltage Engineering and Application (ICHVE 2010), P572, DOI 10.1109/ICHVE.2010.5640768