Compatibility of Transformer Construction Materials with Natural Ester-based Insulating Fluids

被引:13
作者
Wilhelm, H. M. [1 ]
Franch, V. [2 ]
Tulio, L. [2 ]
Franch, A. F. [3 ]
机构
[1] DIAGNO, Diagno Mat & Meio Ambiente, BR-82510060 Curitiba, Parana, Brazil
[2] Inst Dev Technol, LACTEC, Dept Chem Technol, BR-81531990 Curitiba, Parana, Brazil
[3] COPEL, Co Paranaense Energia, BR-18045 Curitiba, Parana, Brazil
关键词
Compatibility; insulating oil; natural ester insulating oil; construction materials; transformer;
D O I
10.1109/TDEI.2015.004755
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The main objective of this study was to evaluate the effect of transformer construction materials, such as kraft insulation paper, varnish, core steel and gasket materials (rubber), on the physicochemical properties of natural ester-based insulating oils (NEIs) and mineral insulating oil (MIO) under heating. We evaluated two NEIs, one formulated with soya oil (Envirotemp FR3) and other with corn oil (Biovolt A). The test specimens were placed in a 1-L jar with 800 mL of insulating oil and then the jar was placed in an oven at 100 degrees C for 716 h. The insulating fluids were analyzed before and after the heating tests by physicochemical analyses, such as kinematic viscosity, acid number (or neutralization number), dissipation factor and interfacial tension for MIO. Properties of the aged reference and the test specimen oils for a standard testing method for compatibility of construction materials with NEIs are proposed. The only parameter that showed variation after the NEI compatibility testing with different materials was the dissipation factor at 90 degrees C. The results show that besides compatibility and aging tests, mechanical tests for the gasket or seal materials should also be performed to conclude whether a material is suitable for construction of transformers insulated with NEIs.
引用
收藏
页码:2703 / 2708
页数:6
相关论文
共 16 条
  • [1] [Anonymous], 2010, D573 ASTM INT
  • [2] [Anonymous], 2011, D3455 ASTM INT
  • [3] [Anonymous], 2012, D471 ASTM INT
  • [4] [Anonymous], 2013, 14274 ABNT NBR
  • [5] [Anonymous], 2008, D6871 ASTM INT
  • [6] [Anonymous], 2009, IEEE Std C57.104-2008 (Revision of IEEE Std C57.104-1991) - Redline, P1
  • [7] ASTM, 2013, ASTM D412
  • [8] Astm, 2010, D2240 ASTM INT
  • [9] A comparison of the impregnation of cellulose insulation by ester and mineral oil
    Dai, J.
    Wang, Z. D.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (02) : 374 - 381
  • [10] Gómez NA, 2014, IEEE T DIELECT EL IN, V21, P1071, DOI [10.1109/TDEI.2014.6832250, 10.1109/TDEI.2013.004161]