Multi-Resonance Control and Phase Margin Compensation Method of Grid-Connected Inverter Based on Voltage and Current Feedforward

被引:0
作者
Hou, Jingwen [1 ]
Wang, Chengsheng [1 ]
Duan, Wei [2 ]
Lan, Zhiming [2 ]
Jiang, Jun [2 ]
Yang, Qiongtao [2 ]
机构
[1] Inst Met Ind, Automat Res & Design, Beijing, Peoples R China
[2] Beijing Aritime Intelligent Control Co LTD, Beijing, Peoples R China
来源
2022 25TH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS (ICEMS 2022) | 2022年
关键词
grid-connected inverter; grid voltage feedforward; LCL-filter; active damping; multi-resonance; phase margin compensation;
D O I
10.1109/ICEMS56177.2022.9982934
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, the feedforward strategy of grid voltage is adopted to suppress the influence on grid-connected current caused by grid voltage. To eliminate the resonant peak of the LCL type filter, the capacitive current feedforward strategy is used to provide active damping. For the weak current network, a multi-resonance link is added based on grid voltage feedforward, for keeping the feedback characteristics only at the main low-frequency harmonics of the power grid and increasing the phase margin in the middle and high frequency band of the resonance frequency. To overcome the instability risk caused by multi-resonance, the phase margin compensator is added to the current loop to improve the robustness of the inverter to the grid impedance.
引用
收藏
页数:6
相关论文
共 50 条
[21]   Grid-Current Control With Inverter-Current Feedback Active Damping for LCL Grid-Connected Inverter [J].
Upadhyay, Nitin ;
Padhy, Narayana Prasad ;
Agarwal, Pramod .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2024, 60 (01) :1738-1749
[22]   A delay compensation method based on a biquad filter for an LCL-type grid-connected inverter [J].
Zhao T. ;
Li J. ;
Gao N. ;
Tian P. .
Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2024, 52 (08) :145-157
[23]   Effect of Low Switching Frequency on Control Link of Grid-connected Inverter and Compensation Method [J].
Zhang Z. ;
Jing L. ;
Zhao Y. ;
Wu X. ;
Wang J. ;
Yang J. .
Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2020, 44 (17) :111-119
[24]   Low Voltage Ride Through Control Method of Photovoltaic Grid-connected Inverter Based on Model Current Predictive Control [J].
Shang, Liqun ;
Li, Pengwei ;
Li, Zhuojun .
PROCEEDINGS OF THE 30TH CHINESE CONTROL AND DECISION CONFERENCE (2018 CCDC), 2018, :5209-5214
[25]   Resonance suppression for grid-connected multi-inverter based on active damping method [J].
He G.-F. ;
Xu D.-H. .
He, Guo-Feng, 1600, Editorial Department of Electric Machines and Control (21) :62-68
[26]   Lyapunov Based Current Control Scheme for Grid-Connected Inverter [J].
Zhang, Wei ;
Liu, Hongpeng .
PROCEEDINGS OF THE 15TH IEEE CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ICIEA 2020), 2020, :1237-1241
[27]   An improved grid voltage observation method for grid-connected inverter [J].
Song, Shuping ;
Sun, Xiaobo ;
Zhang, Zhihao ;
Bao, Huping .
INTERNATIONAL JOURNAL OF MODELLING IDENTIFICATION AND CONTROL, 2024, 44 (01) :88-96
[28]   Passivity-Based Stabilization of a Grid-Connected Three-Phase Inverter System with Feedforward Control [J].
Kato T. ;
Inoue K. ;
Yamamoto Y. ;
Yomura K. .
IEEJ Transactions on Electronics, Information and Systems, 2020, 140 (11) :1189-1197
[29]   A Delay Compensation Method to Improve the Current Control Performance of the LCL-type Grid-connected Inverter [J].
Wang L. ;
Sun P. ;
Xue T. ;
Li Q. ;
Du X. ;
Luo Q. .
Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2020, 40 (19) :6320-6329
[30]   Extended Stable Boundary of LCL-Filtered Grid-Connected Inverter Based on An Improved Grid-Voltage Feedforward Control [J].
Lu, Minghui ;
Xin, Zhen ;
Wang, Xiongfei ;
Beres, Remus Narcis ;
Blaabjerg, Frede .
2016 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2016,