Measurement of Flux Density Distribution on 100kVA 3-Phase Distribution Transformer Assembled With 90° T-Joint and Mitred Lap Corner Joint with Stagger Yoke by Using Search Coil

被引:1
作者
Ahmad, Dina M. M. [1 ]
Daut, I. [1 ]
机构
[1] UniMAP, Sch Elec Syst Eng & Power Elect & Elec Machine De, Perlis, Malaysia
来源
2008 IEEE 2ND INTERNATIONAL POWER AND ENERGY CONFERENCE: PECON, VOLS 1-3 | 2008年
关键词
Transformer core; flux distribution; power loss; search coil;
D O I
10.1109/PECON.2008.4762698
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
This paper describes the result of measurement of flux distribution on 100kVA 3phase distribution transformer assembled with 90 degrees T-joint and mitred lap corner joint with stagger yoke. The measurement involves the variation of flux. The flux density distributions have been measured using no load test by arrays of search coil in M5 (CGO) grades material of transformer core laminations. The localised flux density at the outer 90 degrees T-joint is 90 mT and rises to be 198 mT at the inner 90 degrees T-joint and the localised nux density at the outer corner-joint is 81 mT and rises to be 149 mT at the inner corner-joint when the transformer core energized 1.5 T 50Hz. A small amount of flux deviation from the rolling direction occurs at the overlap.
引用
收藏
页码:1404 / 1407
页数:4
相关论文
共 10 条
[1]  
Beckley P., 2002, Electrical Steels for Rotating Machines
[2]  
Dasgupta I., 2002, Design of transformers
[3]   SOME EFFECTS OF CORE BUILDING ON LOCALIZED LOSSES AND FLUX DISTRIBUTION IN A 3-PHASE TRANSFORMER CORE ASSEMBLED FROM POWERCORE STRIP [J].
DAUT, I ;
MOSES, AJ .
IEEE TRANSACTIONS ON MAGNETICS, 1990, 26 (05) :2002-2004
[4]  
DAUT I, 2008, COMP LOCALIZED POWER
[5]  
DAUT I, 1992, THESIS U WALES
[6]  
DAUT I, 2008, MEASUREMENT FLUX DIS
[7]  
DINA MM, 2004, 2 INT POW ENG OPT C
[8]  
Harlow J.H., 2004, Electric Power Transformer Engineering
[9]  
JONES AJ, 1974, IEEE TANS ON MAG, V10
[10]  
MOSES AJ, 1972, IEEE TANS ON MAG, V8