Chip to Facility Ramifications of Containment Solution on IT Airflow and Uptime

被引:26
作者
Alissa, Husam A. [1 ]
Nemati, Kourosh [1 ]
Sammakia, Bahgat G. [1 ]
Schneebeli, Ken [2 ,3 ]
Schmidt, Roger R. [2 ,3 ]
Seymour, Mark J. [4 ,5 ]
机构
[1] SUNY Binghamton, Dept Mech Engn, Binghamton, NY 13902 USA
[2] IBM Corp, Poughkeepsie, NY 95134 USA
[3] IBM Corp, Poughkeepsie, NY 12601 USA
[4] Future Facil Ltd, London SE1 7HX, England
[5] Future Facil Ltd, San Jose, CA 95110 USA
来源
IEEE TRANSACTIONS ON COMPONENTS PACKAGING AND MANUFACTURING TECHNOLOGY | 2016年 / 6卷 / 01期
基金
美国国家科学基金会;
关键词
Back pressure; characterization; containment; data center (DC); flow curve; flow regions; IT equipment; mission critical; reliability;
D O I
10.1109/TCPMT.2015.2508453
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
We developed a generalized testing methodology in which IT fans' internal and external impedance effects are collapsed into a single curve (i.e., flow curve). Such curves can give accurate flow rate predictions of the IT equipment based on RPM logging. Flow curves cover the three possible airflow regions for IT in a contained environment. The experimental procedure is introduced to rank IT equipment based on its air systems, and the flow regions are correlated with the CPU performance. The strength of the IT air system is characterized by the free delivery and the critical pressure points. In addition, the experimentally obtained active flow curves can be used as a numerical boundary condition in various containment designs. Accordingly, for the first time in the literature, the aerodynamic interaction of IT with different air systems in the containment (i.e., BladeCenters, servers, and switches) can numerically be investigated. It is found that stacking IT in a contained environment with no physical consideration can lead to radical reliability problems. The region of reverse flow is discovered to be very possible upon events in the data center. In such a case, the weak IT (e.g., 1U switch) behaves as an open leakage into the sealed containment. On the other hand, at the critical pressure point, minimum forced convection occurs in the weak IT, leading to CPU overheating.
引用
收藏
页码:67 / 78
页数:12
相关论文
共 32 条
  • [1] Abdelmaksoud W.A., 2010, 2010 12th IEEE Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems, P1
  • [2] Alissa H, 2014, INTSOC CONF THERMAL, P771, DOI 10.1109/ITHERM.2014.6892359
  • [3] Innovative Approaches of Experimentally Guided CFD Modeling for Data Centers
    Alissa, H. A.
    Nemati, K.
    Sammakia, B.
    Ghose, K.
    Seymour, M.
    Schmidt, R.
    [J]. 2015 31ST ANNUAL SEMICONDUCTOR THERMAL MEASUREMENT, MODELING & MANAGEMENT SYMPOSIUM (SEMI-THERM), 2015, : 176 - 184
  • [4] Alissa H. A., 2015, P INTERPACK SAN FRAN
  • [5] Alissa H. A., 2015, P INTERPACK SAN FRAN
  • [6] Alkharabsheh S. A., 2013, P INTERPACK BURL CA
  • [7] *AM SOC HEAT REFR, 2005, DAT EQ POW TRENDS CO
  • [8] [Anonymous], 2013, COST DAT CTR OUT
  • [9] [Anonymous], 2015, 6SIGMA 9 3 US MAN
  • [10] ASHRAE Technical Committee 9.9, 2015, 99 ASHRAE TECHN COMM