Indices for selecting the best location of PSSs or FACTS-based stabilisers in multimachine power systems: A comparative study

被引:50
|
作者
Wang, HF
Swift, FJ
Li, M
机构
[1] Department of Electrical and Electronic Engineering, Manchester Metropolitan University, John Dalton Building, Manchester M1 5GD, Chester Street
关键词
FACTS-based stabiliser; PSS; oscillation stability; damping torque analysis; residue; multimachine power system;
D O I
10.1049/ip-gtd:19970736
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
One of the first stages in the design of a PSS or a FACTS-based stabiliser in a multimachine power system is the selection of the best installing location. Among the most popular techniques used to perform this selection, two groups of indices from the residue and the damping torque analysis (DTA) methods were considered to be different both in their calculation and principle of derivation. However, the authors have found that these two groups of indices are in fact closely related to each other, and indeed are equivalent under certain conditions. In the paper, this finding is presented by considering the relationship between these two groups of indices and shows how equivalence may be concluded. Thus a deeper insight into the residue and DTA methods emerges which facilitates a comparison between the accuracy of these indices.
引用
收藏
页码:155 / 159
页数:5
相关论文
共 41 条