A Novel Approach for Arcing Fault Detection for Medium-/Low-Voltage Switchgear

被引:10
|
作者
Lee, Wei-Jen [1 ]
Sahni, Mandhir [1 ]
Methaprayoon, K. [1 ]
Kwan, Chiman [2 ]
Ren, Zhubing [2 ]
Sheeley, Joseph M. [3 ]
机构
[1] Univ Texas Arlington, Energy Syst Res Ctr, Dept Elect Engn, Arlington, TX 76019 USA
[2] Intelligent Automat Inc, Rockville, MD 20855 USA
[3] Arnold AFB, Arnold Engn Dev Ctr, Aerosp Testing Alliance, Facil & Test Technol Sect, Tullahoma, TN 37389 USA
关键词
Arcing fault; differential protection and harmonics; switchgear;
D O I
10.1109/TIA.2009.2023559
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Switchgear arcing faults have been a primary cause for concern for the manufacturing industry and safety personnel alike. The deregulation of the power industry being in full swing and the ever-growing competitiveness in the distribution sector call for the transition from preventive to predictive maintenance. Switchgears form an integral part of the distribution system in any power system setup. Keeping in mind the switchgear arcing faults, the aforementioned transition applies, most of all, to the switchgear industry. Apart from the fact that it is the primary cause of serious injuries to electrical workers worldwide, switchgear arcing faults directly affect the quality and continuity of electric power to the consumers. A great amount of technological advancement has taken place in the development of arc-resistant/proof switchgears. However, most of these applications focus on minimizing the damage after the occurrence of the arcing fault. The problem associated with the compromise on the quality and continuity of electric power in such a scenario still awaits a technical as well as economically feasible solution. This paper describes the development of a novel approach for the detection of arcing faults in medium-/low-voltage switchgears. The basic concept involves the application of differential protection for the detection of any arcing within the switchgear. The new approach differs from the traditional differential concept in the fact that it employs higher frequency harmonic components of the line current as the input for the differential scheme. Actual arc-generating test benches have been set up in the Power System Simulation Laboratory at the Energy Systems Research Center to represent both medium-and low-voltage levels. Hall effect sensors in conjunction with Data Acquisition in LabVIEW are employed to record the line current data before, during, and after the arcing phenomenon. The methodology is first put to test via simulation approach for medium-voltage levels and then corroborated by actual hardware laboratory testing for low-voltage levels. The plots derived from the data gathering and simulation process clearly underline the efficiency of this approach to detect switchgear arcing faults. Both magnitude and phase differential concepts seem to provide satisfactory results. Apart from the technical efficiency, the approach is financially feasible, considering the fact that the differential protection is already being comprehensively employed worldwide.
引用
收藏
页码:1475 / 1483
页数:9
相关论文
共 50 条
  • [31] Value of Insulated Bus Bars in Reducing Arcing Fault Duration in Low-Voltage Systems
    Rajvanshi, Rahul
    Hawkins, Tom
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2016, 52 (02) : 1280 - 1284
  • [32] Multiobjective Approach for Medium- and Low-Voltage Planning of Power Distribution Systems Considering Renewable Energy and Robustness
    Rupolo, Diogo
    Pereira Junior, Benvindo Rodrigues
    Contreras, Javier
    Sanches Mantovani, Jose Roberto
    ENERGIES, 2020, 13 (10)
  • [33] SELECTION OF DUROMER MATERIALS FOR LOW-VOLTAGE SWITCHGEAR
    TENDIS, O
    KUNSTSTOFFE-PLASTICS, 1978, 25 (03): : 43 - 43
  • [34] COMPREHENSIVE METHOD FOR EVALUATION OF MEDIUM- AND LOW-VOLTAGE DISTRIBUTION NETWORK OPERATING STATE
    Su S.
    Su S.
    You Y.
    Zou Y.
    Technical Electrodynamics, 2020, 2020 (06): : 1 - 4
  • [35] A Testbed for Energy Pilferage Simulation for Medium- And Low-Voltage Electricity Distribution Networks
    Alfonso, Leah Christina
    Batad, Michelle
    Pedrasa, Michael Angelo
    2019 9TH INTERNATIONAL CONFERENCE ON POWER AND ENERGY SYSTEMS (ICPES), 2019,
  • [36] Determination of the cause of arcing faults in low-voltage switchboards
    Land, H. Bruce, III
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2008, 44 (02) : 430 - 436
  • [37] Possibilities of Silver Savings in Low-voltage Switchgear.
    Paukert, Josef
    Elektrotechnicky obzor, 1982, 71 (04): : 193 - 197
  • [38] Future trends in development of low-voltage vacuum switchgear
    Chaly, AM
    Cunningham, J
    ISDEIV: XXTH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, PROCEEDINGS, 2002, 20 : 22 - 24
  • [39] MNS - A PROVEN MODULAR LOW-VOLTAGE SWITCHGEAR SYSTEM
    CHROBAK, E
    POLLAK, M
    BROWN BOVERI REVIEW, 1986, 73 (05): : 224 - 230
  • [40] A Combined High-, Medium-, and Low-Voltage Test System for Stability Studies with DERs
    Escobar, Francisco
    Garcia, Jorge
    Viquez, Juan M.
    Valverde, Gustavo
    Aristidou, Petros
    ELECTRIC POWER SYSTEMS RESEARCH, 2020, 189